background image

6.  Replace the hex nuts removed in Step 3. Ensure the 

star  washer  is  in  place  over  the  nut  at  the  ground 
location under the power board. For proper grounding 
the washer must be located under the power board. 

7.  Reconnect wiring to neon lamp, HV1, HV2, and 24 V 

terminals on the new power board. See Fig. 5. 

8.  Return power to Air Cleaner. Test power board. 
9.  Replace power box cover panel and close cover. 

Note:

  The power board has been set before shipping. It 

is  not  usually  necessary  to  reset  the  voltage  to  the  new 
load. If you do need to adjust the voltage refer to Setting 
Voltage of Power Board section for more information.

 

 
Testing The 24 V Transformer  

1.  Remove the cover and cover panel to the power box.  
2.  Disconnect the leads of the 24 V transformer from the 

power board. See Fig. 5. Do not short the leads. 

3.  Push a screwdriver into the slot to defeat the interlock 

switch and turn the Air Cleaner 

ON

.  

4.  Measure  the  voltage  across  the  leads  with  a 

voltmeter. Voltage should read 25 - 28 VAC. 

5.  If  no  voltage  is  present,  check  the  voltage  from  the 

system switch. 

6.  If  there  is  voltage  to  the  transformer  but  no  output, 

replace the transformer. 

 
Replacing The 24 V Transformer 

Before  replacing  the  transformer,  check  the 

resistance  across  the  power  board  24  V  input  terminals, 
without  the  transformer  connected.  Resistance  should 
read  above  20K  ohms  with  an  analog  meter  and  above 
4M  ohms  with  a  digital  meter.  If  the  resistance  readings 
are  below  these  values,  the  power  board  may  be  the 
cause of the transformer failure. 

 

Before replacing the  24  V  transformer, turn 

OFF

 the 

power to the Air Cleaner at the source. 
1.  Remove the cover and power box cover panel. 
2.  Disconnect the secondary leads from the transformer 

to the 24 V terminals on the power board. See Fig. 5. 

3.  Remove  the  black  primary  lead  from  the  system 

switch.  Remove  the  wire  nut  from  the  other  primary 
lead.  

4.  Remove  the  2  hex  head  nuts  and  washers  from  the 

transformer studs. 

5.  Remove the transformer. 
6.  Place  new  transformer  over  studs  and  re-install  the 

hex head nuts and washers to secure into place. 

7.  Connect  the  secondary  leads  (white)  to  the  24  V 

terminals on the power board (P1 & P2). 

8.  Place one black lead on the system switch terminal. 
9.  Place  the  other  black  lead  with  the  two  white  leads 

from the terminal block and connect with the wire nut 
you removed earlier. 

10.  Replace power box cover panel and close cover. 

11.  Turn 

ON

 the power to the Air Cleaner and test. 

 
Setting Voltage Of Power Board

 

Voltage on the power board may drop below required 

level  when  the  installation  area  is  too  damp,  too  cold  or 
the input power to the unit is low. Voltage on power board 
may  be  too  high  when  the  installation  area  is  too  dry  or 
too hot or the input power to the unit is high. By adjusting 
the  HV  Adj.  potentiometer,  the  voltage  can  be  set  to 
optimum  level.  A  high  voltage  meter  capable  of 
measuring  10,000  VDC  is  required.  To  test  and  adjust 
voltage level, perform the following procedure: 
1.  Turn  the  Air  Cleaner 

ON

  and  wait  5  minutes  before 

checking voltage to allow voltage on cell to stabilize. 

2.  Turn the Air Cleaner 

OFF

, with the cell in the unit. 

3.  Remove cover and the power box cover panel. 
4.  Connect the ground of the high  voltage meter to the 

ground stud in the power box. 

5.  Turn the Air Cleaner 

ON

 and defeat interlock switch. 

6.  Measure  the  voltage  at  HV1  and  HV2  on  the  power 

board.  

7.  Adjust  the  HV  Adj.  potentiometer  until  the  voltage 

reading  matches  the  voltage  in  Fig.  5.  Adjusting  the 
potentiometer 

clockwise  decreases

 the voltage and 

turning 

counter-clockwise increases

 the voltage. 

8.  Turn 

OFF

 the Air Cleaner. 

9.  Remove the high voltage meter. 
10.  Replace the power box cover panel and close cover. 
11.  Turn 

ON

 the Air Cleaner. 

 

Setting Approximate Voltage Without High Voltage 
Meter 

A high voltage meter should be used to set the high 

voltage. If one is not available, this method can be used. 
This will only set an approximate voltage. After using this 
method,  the  voltage  should  be  reset  with  a  high  voltage 
meter as soon as possible. 
1.  Remove  power  box  cover  panel,  with  the  cell  in  the 

unit. 

2.  Turn  the  HV  Adj.  potentiometer  fully  counter-

clockwise.  The  Air  Cleaner  may  arc  or  snap  at  this 
point. 

3.  Turn  the  HV  Adj.  potentiometer  clockwise 

approximately a quarter turn. 

4.  Replace power box cover panel and close cover. 

 
Testing For Voltage At The Cell

 

1.  Remove the cover and power box cover panel. 
2.  The cell must be in the Air Cleaner for this test. 
3.  Turn  the  Air  Cleaner 

ON

  and  defeat  the  safety 

interlock switch.  

4.  Place a plastic handled screwdriver into the direction 

arrow slot. Do not apply excessive force. 

5.  If  there  is  a  good  snap  then  there  is  high  voltage  at 

the cell. 

Содержание SSCB-7 SERIES

Страница 1: ...Operation And Maintenance Manual SSCB 7 SERIES SEMI FLUSH CEILING MOUNTED ELECTRONIC AIR CLEANER IMPORTANT PLEASE READ MANUAL BEFORE INSTALLING OPERATING CLEANING OR SERVICING UNIT...

Страница 2: ...ple of Electrostatic Precipitation Millions of airborne pollutants are drawn through the intake grill on the bottom of the Air Cleaner and first pass through a Prefilter which removes all large visibl...

Страница 3: ...e wiring compartment INSTALLATION 1 Read instructions carefully Failure to do so may result in product damage or injury 2 Make sure the sizing is correct for your application 3 Installation should be...

Страница 4: ...ing is an average wash cycle Stores Offices Computer Conference Rooms 4 Weeks Cafeterias Restaurants Lounges 3 4 Weeks Bars Bingo halls 1 3 Weeks The unit should be checked on a regular basis to deter...

Страница 5: ...tch and transformer to make sure that they are functioning correctly 6 If there is voltage present but the performance light does not come on replace the light 7 The high voltage can be adjusted with...

Страница 6: ...lead with the two white leads from the terminal block and connect with the wire nut you removed earlier 10 Replace power box cover panel and close cover 11 Turn ON the power to the Air Cleaner and te...

Страница 7: ...until a replacement is received 4 Place one end of the loop over the finger at the bottom of the cell 5 Using needle nose pliers grip the other end of wire near the bottom of the top loop Pull the wi...

Страница 8: ...Fig 6 Electrical Schematic With Wired Remote 120 Volt Fig 5 Electrical Schematic 120 Volt 8...

Страница 9: ...mance indicator light is ON Defective power switch Check power switch for continuity with ohmmeter Replace if defective Defective speed selector switch Check switch for continuity with ohmmeter Replac...

Страница 10: ...ncl Grill Gray EACCM7 06G 7 Collecting Cell EACCM7 07 8 Cell Handle EAC14 16 9 Ionizing Wire EAC20 19 10 Safety Interlock Switch EACCM13 10 11 Red Indicator Light EACCM13 11 Description Part Number 12...

Страница 11: ...in 71 0 cm Height 15 in 38 1 cm Weight 70 0 lbs 32 0 kg Input Voltage 120 V 60 Hz Power Consumption maximum 150 Watts Air Flow Hi 712 CFM 1210 m3 hr Medium 575 CFM 977 m3 hr Low 440 CFM 748 m3 hr Moto...

Страница 12: ...General Filters Inc THERE ARE NOT EXPRESS WARRANTIES COVERING THIS ELECTRONIC AIR CLEANER OTHER THAN AS SET FORTH ABOVE THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE A...

Отзывы: