To directly attach the Interface Module and to attach wiring conduits to alarm relays
and control room equipment
The factory installs plugs in the unused entry holes, except one. A red plastic cap is placed into
the remaining hole and must be removed before conduit can be attached to the housing. Each
hole is tapped for ¾ inch NPT threads. If a particular entry hole is not used, it must be plugged
during operation in the field.
NOTE:
Always follow appropriate local or national wiring and installation requirements and
use approved conduit plugs at the time of installation.
When a TS4000 Interface Module is attached to the Base Unit or a remote junction box for
remote configuration, it must be screwed into the Base Unit / remote junction box housing using
five to seven turns to ensure that the explosion proof integrity of the housing is maintained.