20
TS4000
The following procedure is for attaching wiring to connectors in the TS4000 terminal blocks
TB1, TB2, and TB3.
To Attach Wiring to a TS4000 Terminal Block
1. Remove the Base Unit enclosure cover by loosening the four captive screws and lifting the
cover straight up.
2. In the terminal block connector, insert a screwdriver into the orange tab and press down,
opening the terminal.
3. Insert the 0.43 inch stripped wire into the terminal and release the orange tab to clamp the
wire in the terminal. GENTLY tug on the wire to make sure it is locked securely in place.
Figure 10: Terminal Block Connector Detail
3.5.3 Connecting to the Power Supply DC Ground
The TS4000 operates on nominal power of +24 VDC. A primary DC power source must be
connected.
NOTE:
In all cases, the cable run should be as short as possible. Refer to Section 9.5 for the
recommended cable distances between the TS4000 and the power supply.
To Connect the TS4000 to DC Ground
1. Connect the Base Unit terminal block TB1-8 to the power supply Common (OVDC).
2. If the TS4000 is being used with a +24V power supply and an industrial analog to digital (A/D)
converter, you must connect the negative supply (COM) of all three devices.
3. To make ground connections to GM devices, refer to the following table:
Table 6: TS4000 to GM Display Device DC Ground Connections
From
To
TS4000
TA102A TA502A
TB1-8
COM (OVDC)
Rear Pin
30d or 30z
Rear Pin
30d or 30z