Model FL3102
Quick Start Guide
ii
1.3 Detector
Installation
The Model FL3102 Detector is an explosion proof assembly rated for use in
Class I, Divisions 1 & 2, Group B, C & D, Class II, Group E, F & G, and
Class III areas. The detector(s) should be mounted pointing downward so that
dust/moisture will not accumulate on the IR windows. The detector(s) should be
mounted in locations, which will inhibit people or objects from obscuring the
detector’s Cone of Vision.
NOTE –
Before installing these units, please read the warning statement on page
13 of this manual. These units must have a conduit seal installed.
Mounting hardware should be used as shown in Figures 2 and 3.
NOTE –
The swivel (961-003) is rated for Class I, Div 1 & 2, Groups C & D. Use
mounting bracket for Group B areas.
The overall dimensions of the detectors and mounting hardware are shown in
Figure 4.