Model FL3102
35
7.7 FL3102 Operational Mode Command Register Details
7.7.1 Analog
A read returns a value, which is proportional to the 0-20mA output current. The
current is based on a 16-bit value. The master scaling is 0-65535 decimal, which
corresponds to the FL3102 scaling, which is 0-20mA.
7.7.2 Mode
A read returns the fire status mode of the FL3102.
Mode
Decimal
Value
Power-up Delay
1
Warn Non-latching Only
2
Warn & Alarm Non-Latching
3
Warn Latching Only
4
Alarm Latching Only
5
Warn & Alarm Latching
6
Ready State (No Fire)
7
Alarm Test
10
COPM Fault Detected
11
Figure 41 Mode
7.7.3 Status/Error
A read returns the errors that are occurring now, which are indicated by bit
position.
Byte
Function Bit
Position
EPROM Checksum
8
EEPROM Checksum
7
RAM Test
6
Low (24V) Voltage Check
5
Fire Window COPM
4
Fire Sensor COPM
3
Sun COPM
2
Low
Low (12V) Voltage Check
1
Reset Line Shorted
8
High
Not Used
7-1
Figure 42 Status/Error