Generac Power Systems PowerManager 004975-2 Скачать руководство пользователя страница 7

 

 

5

2.1.2 REMOTE 

CONNECTION

To connect remotely via modem, the PM-SC must have been con-

nected to a telephone jack and the phone number must be known. 

Simply start GenLink (see the New Generation GenLink manual) 

and set the connection type to “modem link.” Edit the “User site 

table” and create a new entry for the PM-SC. This is done by sim-

ply clicking on one of the fields shown in the table and entering the 

data. There is one row per entry and to create a new entry, click on 

an empty row. To edit an entry, simply click on the cell to be edited. 

The phone number for the PM-SC is the only value that must be 

entered (its Modbus address is set by default to 100 but can be 

changed via GenLink). All other fields are optional.
Once the data has been edited, click on “Apply” to save the 

changes. Select the desired row from the table by clicking on the 

gray cell to the left of the row and then click “Connect”.

2.1.3 LAN/INTERNET 

CONNECTION

To connect via the Internet or via a local area network (Ethernet 

LAN) a special converter box is required between the PM-SC’s 

RS232 connector and the LAN. This can be obtained by contacting 

the manufacturer's service department. The converter box needs 

to be assigned either a network address, for connection from a PC 

connected to the LAN, or an internet address for remote access. 

In either case the manufacturer recommends the box is installed 

with the aid of a competent IT professional. The “Device installer” 

program (supplied) is used to assign the address and set up the 

RS232 port on the converter. Run the device installer and use 

the "search “ button to find the device on your network. Click on 

the device to bring up extra menu’s in device installer. Click on 

“Configure” and then select “Ports” to set up the device’s RS232 

port. Set the baud rate to match the port in the PM-SC. We suggest 

the following settings for optimal use:

57600 baud

• 

8 data bits

• 

no parity

• 

one stop bit 

• 

no hand shaking

• 
You must ensure this is how you have set the Genlink port (port 

2) on the PM-SC . Note if you need to change the baud rate in the 

PM-SC you must power the panel off and back on again for it to 

take effect. In an MPS configuration you should use the 57600 

baud setting for all communications with the generators (port 0).
Special port re-direction software will need to be installed on the 

PC as well as Genlink, this is supplied with the converter box. 

Use the re-direction software to select an unused port on your PC 

that will be re-directed to the PC’s LAN connection, for example 

com port 8. To select this port, use the “com setup” button and 

click on the port number you want to use. Assign that port to the 

address you have given your converter box via the “Add IP” but-

ton. Enter the address into the “Host” field, and enter 3001 into 

the port field.
When Genlink is started, select the new com port via the tools 

menu as described above. This will then always default to the LAN 

as the method of connection.

3.1  PROGRAMMING THE PM-SC

After connecting, the screen in Figure 3.1 will be displayed. If 

you have any problems connecting such as the wrong Modbus 

address, Genlink has tools to allow you to troubleshoot the con-

nection (see “Connection Problems”).

Figure 3.1

This screen is the mimic of the whole system, showing the com-

mon generator bus connections, the generators and their internal 

bus contactors. The live portions of the circuit will be shown in 

red. The positions of the contactors are actual and will change as 

the generators start. Scrolling around the screen is accomplished 

using the slider bars. The section with the black background at the 

top of the screen refers to the total values on the common genera-

tor bus, and the cyan blocks at the bottom of the screen refer to the 

individual generators. The blue “utility option” meters section will 

only display utility power etc if utility CT’s have been purchased.
To look at a generator’s parameters (i.e to “drill down” to a genera-

tor), click on the generator in question. It is then possible to exam-

ine the generator’s parameters and change them in the normal way 

(see New Generation GenLink manual). A report of the generator’s 

status and settings can be printed.

3.1.1 GENERATOR 

SETTINGS

To program the PM-SC system itself, click on the “Configuration” 

button located to the lower left of the upper display box. The 

screen in Figure 3.2 will appear.
Use the tabs at the top of the screen to go to the desired page. 

The screen above shows the generator settings page. This is 

used to program the PM-SC with information about the connected 

generator sets. Generators can be added or deleted to match the 

installation. 
To add a generator, program it’s details into the right hand data 

entry fields then click on the “Add to list” button to copy it into 

the left hand pane, finally click the “Apply” button to permanently 

save it.

Operation

Содержание PowerManager 004975-2

Страница 1: ...MA 1 Enclosure Model 005039 1 NEMA 3R Enclosure Model 005047 1 NEMA 3R Enclosure with Heater PowerManager System Controller PM SC nOnly qualified electricians or contractors should attempt installatio...

Страница 2: ...munication Issues 9 3 10 Relay Functionality 9 3 11 Backup Modes of Operation 10 3 11 1 Introduction 10 3 11 2 Abbreviations 10 3 11 3 Documents 10 3 11 4 Standard Control System 10 3 11 5 Normal MPS...

Страница 3: ...az ard This symbol points out potential fire hazard This symbol points out potential electrical shock hazard The operator is responsible for proper and safe use of the equip ment The manufacturer stro...

Страница 4: ...Never work on the equipment when physically or mentally fatigued Inspect the generator s regularly and repair or replace all damaged or defective parts immediately Always use factory authorized parts...

Страница 5: ...to local state and national electrical and building codes Comply with regulations the Occupational Safety and Health Administration OSHA has established Also ensure that the generator s is installed...

Страница 6: ...ets with different power ratings Real time clock and calendar included user programmable to set exercisers based on date and time of day Monitoring set up of parameters and commands using New Generati...

Страница 7: ...the PC as well as Genlink this is supplied with the converter box Use the re direction software to select an unused port on your PC that will be re directed to the PC s LAN connection for example com...

Страница 8: ...ot set a leading power factor 3 1 7 SLAVE ADDRESS This is the Modbus slave ID of the generator and must correspond to the Modbus ID setting in the corresponding PM PC control panel Set all the paramet...

Страница 9: ...The base load can be programmed into the Kw setting field The power factor is fixed at 1 00 for exercise and cannot be adjusted 3 2 2 KW AND POWER FACTOR LIMITS These settings are only used to set up...

Страница 10: ...ecking any box Gen1 through 10 tells the system that the checked generator s has been intentionally taken out of service for example for maintenance The PM SC will then not expect that generator to st...

Страница 11: ...TION ISSUES Normally communication problems can be resolved with the help of either the Genlink or Touchscreen com port diagnostic displays see Figures 3 7 and 3 8 Select the diagnostic display then c...

Страница 12: ...g the generators to the bus proportion ally share load across all connected generators disconnect the generators from the Bus and shut the generators down The PM SC also accumulates data from the gene...

Страница 13: ...e for Enabling Manual Backup Operation Using GenLink connect to the PM SC Open the Configuration pull down menu and select Regulator Settings Figure 3 10 Figure 3 10 Regular Settings In the lower left...

Страница 14: ...Status After all the running generators are connected to the Bus the operator must determine what generator power is available and what the load requirements are If there is enough power available for...

Страница 15: ...procedure Go to each generator in the MPS that is in the MANUAL mode and using the generator touch screen main menu select the Diagnostics page Figure 3 17 Figure 3 17 Diagnostics Press the Cancel MA...

Страница 16: ...eration is available with PM PC and PM SC firmware version 2 2H or later Figure 3 20 The automatic backup operation consists of the normal MPS operation with the added ability of each generator PM PC...

Страница 17: ...er is available and what the maximum power needs are If there is enough power available for a given permissive to be active the PM PLS will activate the appropriate permissive signals If a generator s...

Страница 18: ...ch requests When the keyswitch is in the MAN position the PM SC will start the genera tors as though a two wire remote start had been issued This is to allow the system to be activated in the event th...

Страница 19: ...lax errors EITHER 1 Switch on the power to the unit 2 During the initialization phase a menu will appear briefly Press the CONFIG button 3 Now use the CALIBRATE button to calibrate the screen 4 Five c...

Страница 20: ...th the circuit diagram You should refer to this diagram to see that the correct input has operated Outputs from the controller are generally open collector This means that they sink current through a...

Страница 21: ...for customer use 5 User assigned 5 Free for customer use 6 User assigned 6 Free for customer use 7 Auto Led On Front Panel Led 8 User assigned 8 Free for customer use 9 Fault Led On Front Panel Led 1...

Страница 22: ...4 20ma User config channel 12 13 4 20ma User config channel 13 14 4 20ma User config channel 14 15 4 20ma User config channel 15 16 4 20ma User config channel 16 17 4 20ma User config channel 17 18 B...

Страница 23: ...E4086 in the back of this manual 1 Ensure that utility power is OFF at this point 2 Connect 18AWG or heavier double insulated wire fused at the source to terminals TB2 1 2 3 in the PM SC and run this...

Страница 24: ...tween generators should only have one end of the shield connected 7 Connect the standard telephone jack to a telephone line using an RJ 11 type cable 8 If an optional Annunciator is to be used connect...

Страница 25: ...23 Notes...

Страница 26: ...24 Notes...

Страница 27: ...25 Notes...

Страница 28: ...26 Installation Diagrams NEMA 1 Drawing No 0E7619 C...

Страница 29: ...27 NEMA 1 Drawing No 0E7619 C Installation Diagrams...

Страница 30: ...28 Installation Diagrams NEMA 3R Drawing No 0H3175 A...

Страница 31: ...29 NEMA 3R Drawing No 0H3175 A Installation Diagrams...

Страница 32: ...Parts shipment costs are reimbursed at ground shipment rates Costs related to requests for expedited shipping will be the responsibility of the customer 11 Verification of required maintenance may be...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ......

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ...1 DECAL 24V SUPPLY 44 0E7438 1 DECAL POWER MANAGER SC TB6 45 062684 1 LUG SLDLSS 2 0 12 X 11 32 CU 46 067210A 1 DECAL GROUND LUG 47 091472 FT DUCT WIRING 1X1 5 6 FT 48 091472A FT COVER WIRE DUCT 1 IN...

Страница 47: ......

Страница 48: ......

Отзывы: