15

Figure 3.21 — Regular Settings

In the lower left corner of the “Regulator Settings Page” is a sec-

tion called “Backup Paralleling Options”. Enable the “Automatic 

with PLS” setting (Figure 3.22).

Figure 3.22 — Automatic with PLS

Close this window and drill down to each generator PM-PC and 

repeat this operation on each PM-PC. If the PM-PC(s) and the 

PM-SC are not set up the same, power will not be shared correctly 

while operating in backup mode.

Procedure for Entering Automatic Backup Mode:

The following procedure refers to generator numbers. The genera-

tor number is the ModBus address of that generator. Backup mode 

priorities and delays are based on the generator numbers. Also, the 

wiring is specified based on the generator number. Therefore, the 

generators should be numbered sequentially via GenLink starting 

at #1.
The MPS will normally have all PM-SC and PM-PC key switches 

in the AUTO position. If the PM-SC or any PM-PC is no longer 

communicating with the MPS, an alarm will sound on the PM-SC, 

PM-PC, or both. If the utility power is lost at this time, the MPS 

will automatically enter the backup mode. In the automatic backup 

mode, the PM-SC continues to control as much of the system as 

it can. However, the PM-PC(s) that are no longer under the PM-SC 

control will start on their own per the following procedure.
When the utility fails, the ATS(s) activate the remote start signal. 

The remote start signal is connected to all generator PM-PC(s) as 

well as the PM-SC.

The generators will all start and warm up. Only generators #1 

and #2 are able to connect to a dead Bus, so they will connect 

to the Bus when they are ready for load. The link between the two 

generators prevents them from both connecting at the same time. 

As each generator connects, it indicates to the PM-PLS that it has 

done so.
The remaining generators synchronize and connect to the Bus as 

they become ready for load. As each generator connects, it indi-

cates to the PM-PLS that it has done so.
Depending on the PM-PLS programming, it will determine how 

much power is available and what the maximum power needs 

are. If there is enough power available for a given permissive to 

be active, the PM-PLS will activate the appropriate permissive 

signals. 
If a generator should shutdown the PM-PLS will activate the 

appropriate load shed signals to allow the remaining system to 

function. 

Procedure for Exiting Automatic Backup Mode:

If the MPS is operating in automatic backup mode, the ATS(s) will 

need to transfer back to utility before exiting this mode. 
When the utility returns, the ATS(s) should automatically switch 

back to the utility and deactivate the remote start signal. This 

will cause all the generators to disconnect from the Bus, enter 

cooldown, and then shutdown.
When the system is able to return to normal operation, it will do so 

only after the remote start signal to the PM-SC/PM-PC(s) deacti-

vates and all the generators have shutdown.

NOTE:

An MPS will perform better in backup mode with like-sized 

generators than with unlike-sized generators.

3.12  MPS TRANSFER SWITCHES

The PM-SC can be set up to control separate multiple transfer 

switches, these can be either the manufacturer's own commu-

nications enabled switches (MTS), standalone transfer switches 

(GTS), or third party switches. The PM-SC can also be used 

with a SINGLE Soft Load Transfer Switch (STS). Up to eight MTS 

switches can be connected to a PM-SC. For third party or GTS 

switches there are three groups of settings for permissive and 

load shed relays plus a critical load setting. These relays can be 

connected to multiple transfer switches as required.
The PM-SC is designed to work with the manufacturer's genera-

tor sets that have paralleling capability (designated PM-PC). The 

transfer switches supplying the equipment (non-critical) load are 

provided with input signals for start permissive and trip to neutral. 

This allows for flexible system startup and load shedding capabili-

ties. The overall system is known as the Modular Power System 

(MPS). The PM-SC can control generator sets with different power 

ratings, and various rating transfer switches may be used to allow 

system flexibility. A real time clock and calendar is included so the 

user can program the PM-SC to exercise the system as required.

Operation

Содержание PowerManager 004975-2

Страница 1: ...MA 1 Enclosure Model 005039 1 NEMA 3R Enclosure Model 005047 1 NEMA 3R Enclosure with Heater PowerManager System Controller PM SC nOnly qualified electricians or contractors should attempt installatio...

Страница 2: ...munication Issues 9 3 10 Relay Functionality 9 3 11 Backup Modes of Operation 10 3 11 1 Introduction 10 3 11 2 Abbreviations 10 3 11 3 Documents 10 3 11 4 Standard Control System 10 3 11 5 Normal MPS...

Страница 3: ...az ard This symbol points out potential fire hazard This symbol points out potential electrical shock hazard The operator is responsible for proper and safe use of the equip ment The manufacturer stro...

Страница 4: ...Never work on the equipment when physically or mentally fatigued Inspect the generator s regularly and repair or replace all damaged or defective parts immediately Always use factory authorized parts...

Страница 5: ...to local state and national electrical and building codes Comply with regulations the Occupational Safety and Health Administration OSHA has established Also ensure that the generator s is installed...

Страница 6: ...ets with different power ratings Real time clock and calendar included user programmable to set exercisers based on date and time of day Monitoring set up of parameters and commands using New Generati...

Страница 7: ...the PC as well as Genlink this is supplied with the converter box Use the re direction software to select an unused port on your PC that will be re directed to the PC s LAN connection for example com...

Страница 8: ...ot set a leading power factor 3 1 7 SLAVE ADDRESS This is the Modbus slave ID of the generator and must correspond to the Modbus ID setting in the corresponding PM PC control panel Set all the paramet...

Страница 9: ...The base load can be programmed into the Kw setting field The power factor is fixed at 1 00 for exercise and cannot be adjusted 3 2 2 KW AND POWER FACTOR LIMITS These settings are only used to set up...

Страница 10: ...ecking any box Gen1 through 10 tells the system that the checked generator s has been intentionally taken out of service for example for maintenance The PM SC will then not expect that generator to st...

Страница 11: ...TION ISSUES Normally communication problems can be resolved with the help of either the Genlink or Touchscreen com port diagnostic displays see Figures 3 7 and 3 8 Select the diagnostic display then c...

Страница 12: ...g the generators to the bus proportion ally share load across all connected generators disconnect the generators from the Bus and shut the generators down The PM SC also accumulates data from the gene...

Страница 13: ...e for Enabling Manual Backup Operation Using GenLink connect to the PM SC Open the Configuration pull down menu and select Regulator Settings Figure 3 10 Figure 3 10 Regular Settings In the lower left...

Страница 14: ...Status After all the running generators are connected to the Bus the operator must determine what generator power is available and what the load requirements are If there is enough power available for...

Страница 15: ...procedure Go to each generator in the MPS that is in the MANUAL mode and using the generator touch screen main menu select the Diagnostics page Figure 3 17 Figure 3 17 Diagnostics Press the Cancel MA...

Страница 16: ...eration is available with PM PC and PM SC firmware version 2 2H or later Figure 3 20 The automatic backup operation consists of the normal MPS operation with the added ability of each generator PM PC...

Страница 17: ...er is available and what the maximum power needs are If there is enough power available for a given permissive to be active the PM PLS will activate the appropriate permissive signals If a generator s...

Страница 18: ...ch requests When the keyswitch is in the MAN position the PM SC will start the genera tors as though a two wire remote start had been issued This is to allow the system to be activated in the event th...

Страница 19: ...lax errors EITHER 1 Switch on the power to the unit 2 During the initialization phase a menu will appear briefly Press the CONFIG button 3 Now use the CALIBRATE button to calibrate the screen 4 Five c...

Страница 20: ...th the circuit diagram You should refer to this diagram to see that the correct input has operated Outputs from the controller are generally open collector This means that they sink current through a...

Страница 21: ...for customer use 5 User assigned 5 Free for customer use 6 User assigned 6 Free for customer use 7 Auto Led On Front Panel Led 8 User assigned 8 Free for customer use 9 Fault Led On Front Panel Led 1...

Страница 22: ...4 20ma User config channel 12 13 4 20ma User config channel 13 14 4 20ma User config channel 14 15 4 20ma User config channel 15 16 4 20ma User config channel 16 17 4 20ma User config channel 17 18 B...

Страница 23: ...E4086 in the back of this manual 1 Ensure that utility power is OFF at this point 2 Connect 18AWG or heavier double insulated wire fused at the source to terminals TB2 1 2 3 in the PM SC and run this...

Страница 24: ...tween generators should only have one end of the shield connected 7 Connect the standard telephone jack to a telephone line using an RJ 11 type cable 8 If an optional Annunciator is to be used connect...

Страница 25: ...23 Notes...

Страница 26: ...24 Notes...

Страница 27: ...25 Notes...

Страница 28: ...26 Installation Diagrams NEMA 1 Drawing No 0E7619 C...

Страница 29: ...27 NEMA 1 Drawing No 0E7619 C Installation Diagrams...

Страница 30: ...28 Installation Diagrams NEMA 3R Drawing No 0H3175 A...

Страница 31: ...29 NEMA 3R Drawing No 0H3175 A Installation Diagrams...

Страница 32: ...Parts shipment costs are reimbursed at ground shipment rates Costs related to requests for expedited shipping will be the responsibility of the customer 11 Verification of required maintenance may be...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ......

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ...1 DECAL 24V SUPPLY 44 0E7438 1 DECAL POWER MANAGER SC TB6 45 062684 1 LUG SLDLSS 2 0 12 X 11 32 CU 46 067210A 1 DECAL GROUND LUG 47 091472 FT DUCT WIRING 1X1 5 6 FT 48 091472A FT COVER WIRE DUCT 1 IN...

Страница 47: ......

Страница 48: ......

Отзывы: