Operation
Owner’s Manual for 60 Hz Air-Cooled Generators
15
Auxiliary Shutdown Switch
All generators are equipped with an external means of
shutting down the generator which complies with the latest
NEC code requirement. The primary generator shutdown
sequence is described in
While Under Load Or During A Utility Outage
.
See
. There is an auxiliary shutdown switch on
the exterior of the generator back panel. This switch
shuts down the generator and disables restarts.
Figure 3-5. External Auxiliary Shutdown Switch
(all models)
NOTE:
Whenever possible, perform the primary
shutdown procedure before disabling the generator with
the auxiliary shutdown switch.
See
. 16-22 kW generators also have an
auxiliary shutdown switch located inside the generator.
Figure 3-6. Internal Auxiliary Shutdown Switch (16-22kW)
The generator will not start if either switch is OPEN (O).
The controller displays an “Auxiliary Shutdown” alarm,
and the red LED “Alarm” light illuminates. To clear this
condition, set the switch or switches to CLOSED (I).
Clear the alarm by pressing the OFF mode button, and
then ENTER. The generator can then be placed back in
AUTO or MANUAL mode.
Control Panel Interface
See
. The control panel interface (A) is located
under the enclosure lid. Verify both the left and right side
locks are unlocked before attempting to lift the lid of the
enclosure. Open the lid as directed in
Figure 3-7. Generator Control Panel
The 7.5A fuse is located beneath the rubber cover (B) to
the right of the control panel.
Verify both left and right side locks are securely out of
the way before closing the unit.
All appropriate panels must be in place during any
operation of the generator. This includes operation by a
servicing technician while conducting troubleshooting
procedures.
Using the AUTO/OFF/MANUAL
Interface
NOTE:
Damage caused by mis-wiring of interconnect
wires is not warrantable.
005491
CAUTION
(000399)
Equipment Damage. The auxiliary shutdown switch is
not to be used to power down the unit under normal
operating circumstances. Doing so will result in
equipment damage.
005492
Button
Description of Operation
AUTO
Activates fully automatic system operation. It
allows the unit to automatically start and
exercise the generator according to the
exercise timer (see
).
The green LED flashes when the automatic
transfer switch converts to generator power
during a utility power outage.
OFF
Shuts down the engine and prevents automatic
operation of the unit.
MANUAL
Cranks and starts the generator. Transfer to
standby power will not occur unless there is a
utility failure.
The blue LED flashes when the automatic
transfer switch converts to generator power
during a utility power outage.