Section 3: Operation
Site Prep Verification
The generator must be installed to allow unimpeded airflow
into and out of the generator.
Mechanical and gravity outdoor air intake openings for air
distribution and supply systems must be located not less
than 10 ft (3.05 m) horizontally from the generator
enclosure. See Section 401.4 in the ICC Mechanical
Code for additional information.
Verify all shrubs or tall grasses within 3 ft (0.91 m) of the
intake and discharge louvers on the sides of the
enclosure have been removed. Install the generator on
high ground where water levels will not rise and
endanger it. This unit should not operate in or be
subjected to standing water. Verify all potential water
sources such as water sprinklers, roof run-off, rain gutter
downspouts, and sump pump discharges are directed
away from the generator enclosure.
Generator Enclosure
Enclosure lid is locked prior to shipment. A set of keys is
attached to the cardboard on top of the generator. An
additional set of keys is attached to the pallet bracket on
the front intake end of the generator.
NOTE:
Keys provided with this unit are intended for
service personnel use only.
Opening the Lid
Two locks secure the lid—one on each side (A in
). Open the protective rubber cap to access the keyhole,
and press down on the lid above the side lock and unlock
the latch to properly open the lid.
Repeat for the other side. The lid may appear stuck if
pressure is not applied from the top.
Always verify the side locks are unlocked before
attempting to lift the lid.
Removing the Front Access Panel
Remove the front access panel by lifting it straight up and
out once the lid is open.
Always lift the front access panel straight up before pulling
it away from the enclosure (B and C in
). Do not
pull the panel away from the enclosure before lifting up (D
in
).
Figure 3-1. Side Lock Location and Front Panel Removal
Automatic start-up. Disconnect utility power and
render unit inoperable before working on unit.
Failure to do so will result in death or serious injury.
(000191)
DANGER
001797
A
A
B
C
D
Содержание 0065510
Страница 10: ...Safety Information 6 Owner s Manual for 60 Hz Air Cooled Generators This page intentionally left blank ...
Страница 21: ...Operation Owner s Manual for 60 Hz Air Cooled Generators 17 This page intentionally left blank ...
Страница 28: ...Operation 24 Owner s Manual for 60 Hz Air Cooled Generators This page intentionally left blank ...
Страница 43: ......