General Information
Owner’s Manual for 60 Hz Air-Cooled Generators
11
Protection Systems
The generator may need to run for long periods of time
with no operator present to monitor engine or generator
conditions. The generator is equipped with protection
systems to automatically shut down the unit to protect
against potentially damaging conditions. Some of these
systems include:
Alarms
:
Warnings:
The control panel contains a display alerting the operator
when a fault condition occurs. The above list is not all-
inclusive. See
for more information about
alarms and control panel operation.
NOTE:
A warning indicates a condition on the generator
which should be addressed, but will not shut down the
generator. An alarm shuts down the generator to protect
the system from any damage. In the event of an alarm,
an owner can clear the alarm and restart the generator
prior to contacting an IASD. Contact an IASD if the
intermittent issue occurs again.
Emission Information
The United States Environmental Protection Agency (US
EPA) (and California Air Resources Board (CARB), for
engines/equipment certified to California standards)
requires that this engine/equipment complies with
exhaust and evaporative emissions standards. Locate
the emissions compliance decal on the engine to
determine applicable standards. For emissions warranty
information, please reference the included emissions
warranty. Follow the maintenance specifications in
to ensure the engine complies with
applicable emissions standards for the duration of the
product’s life.
This generator is certified to operate on liquid propane
vapor fuel or pipeline natural gas.
The Emission Control System code is EM (Engine
Modification). The Emission Control System on this
generator consists of the following:
:
Fuel Requirements
The engine has been fitted with a dual fuel carburetion
system. The unit will run on natural gas or LP gas
(vapor), but it has been factory set to run on natural gas.
The fuel system will be configured for the available fuel
source during installation.
Recommended fuels should have a BTU content of at least
1000 BTUs per ft
3
(37.26 megajoules per m
3
) for natural
gas, or at least 2500 BTUs per ft
3
(93.15 megajoules per
m
3
) for LP gas (vapor).
NOTE:
If converting to LP gas from natural gas, a
minimum LP tank size of 250 gal (946 L) is recommended.
See the installation manual for complete procedures and
details.
Battery Requirements
12 volts, Group 26R-540CCA minimum or Group 35AGM-
650CCA minimum (not included with unit.) See
for proper battery maintenance procedures.
Battery Charger
The battery charger is integrated into the control panel
module in all models. It operates as a smart charger,
ensuring output charging levels are safe and
continuously optimized to promote maximum battery life.
A kit is provided to install a fuse in the transfer switch for
the T1 battery charger connection. Follow the installation
instructions provided with the kit.
NOTE:
Do not use external battery chargers.
Engine Oil Requirements
See
in the Maintenance
section for proper oil viscosity.
•
High Temperature
•
Low Oil Pressure
•
Overcrank
•
Overspeed
•
Overvoltage
•
Undervoltage
•
Overload
•
Underspeed
•
RPM Sensor Loss
•
Controller Fault
•
Wiring Error
•
Stepper Overcurrent
•
Charger Warning
•
Charger Missing AC
•
Low Battery
•
Battery Problem
•
Exercise Set Error
•
USB Warning
•
Download Failure
System
Components
Air Induction
- Intake Manifold
- Air Cleaner
Fuel Metering
- Carburetor and Mixer Assembly
- Fuel Regulator
Ignition
- Spark Plug
- Ignition Module
Exhaust
- Exhaust Manifold
- Muffler
(000105)
DANGER
Explosion and Fire. Fuel and vapors are
extremely flammable and explosive. Add fuel
in a well ventilated area. Keep fire and spark
away. Failure to do so will result in death
or serious injury.
Содержание 0065510
Страница 10: ...Safety Information 6 Owner s Manual for 60 Hz Air Cooled Generators This page intentionally left blank ...
Страница 21: ...Operation Owner s Manual for 60 Hz Air Cooled Generators 17 This page intentionally left blank ...
Страница 28: ...Operation 24 Owner s Manual for 60 Hz Air Cooled Generators This page intentionally left blank ...
Страница 43: ......