General Information
10
Owner’s Manual for 60 Hz Air-Cooled Generators
Specifications
Generator
Engine
A detailed specification sheet for your particular generator is available from your local Independent Authorized Service
Dealer (IASD).
Model
9 kW
11 kW
16 kW
20 kW
22 kW
Rated Voltage
240
Rated Maximum Load
Current (Amps) at Rated
Voltage with LP*
37.5
45.8
66.6
83.3
91.7
Main Line Circuit Breaker
(Generator Disconnect)
40 Amp
50 Amp
70 Amp
90 Amp
100 Amp
Phase
1
Rated AC Frequency
60 Hz
Battery Requirement
(Field supplied)
12 volts, Group 26R-540CCA Minimum or Group 35AGM-650CCA Minimum
(see
Enclosure
Aluminum
Weight (lb/kg)
(without battery)
340/154
348/158
409/186
448/203
466/211
Normal Operating Range
This unit is tested in accordance to UL 2200 standards with an operating temperature of -20 °F (-29 °C) to
122 °F (50 °C). For areas where temperatures fall below 32 °F (0 °C) a cold weather kit is recommended.
When operated above 77 °F (25 °C), there may be a decrease in engine power. See
These generators are rated in accordance with UL 2200, Safety Standard for Stationary Engine Generator Assemblies, and CSA-C22.2 No. 100-04
Standard for Motors and Generators.
* Natural gas ratings will depend on specific fuel joules/BTU content. Typical derates are between 10-20% off the LP gas rating.
Model
9 kW
11 kW
16/20/22 kW
Type of Engine
G-Force 400 Series
G-Force 500 Series
G-Force 1000 Series
Number of Cylinders
1
2
2
Displacement
426 cc
530 cc
999 cc
Cylinder Block
Aluminum with cast iron sleeve
Recommended Spark Plug
See
Spark Plug Gap
0.020 in (0.508 mm)
0.030 in (0.76 mm)
0.040 in (1.02 mm)
Valve Clearance
0.002–0.004 in
(0.05–0.1 mm)
0.002–0.004 in
(0.05–0.1 mm)
0.002–0.004 in
(0.05–0.1 mm)
Starter
12 VDC
Oil Capacity Including Filter
Approx. 1.1 qt (1.03 L)
Approx. 1.7 qt (1.6 L)
Approx. 1.9 qt (1.8 L)
Recommended Oil Filter
See
Recommended Air Filter
See
Engine power is subject to and limited by such factors as fuel BTU/joules, ambient temperature, and altitude. Engine power decreases approximately
3.5% for each 1000 ft (304.8 m) above sea level, and also will decrease about 1% for each 10 °F (6 °C) above 60 °F (15 °C) ambient temperature.