 Commissioning

CAUTION!   Wear  personal  protective  clothing  such  as  goggles  and  protective 

gloves!

  Make sure that the suction and pressure line shut-off valves are open.

  With the compressor switched off, add the liquid refrigerant directly to the condenser or receiver, 

breaking the vacuum.

  If the refrigerant needs topping up after starting the compressor, it can be topped up in vapour 

form on the suction side, or, taking suitable precautions, also in liquid form at the inlet to the 

evaporator.

 INFO! 

 

Avoid overfilling the system with refrigerant!

     

  In  order  to  prevent  shifts  in  concentration,  zeotropic  refrigerant 

blends (e.g. R410A) must always only be added to the refrigerating 

system in liquid form.

     

  Do not pour liquid refrigerant through the suction line shut-off val

-

ve on the compressor.

      

  It is not permissible to mix additives with the oil and refrigerant.

6.5  Refrigerant charge

6.6  Start-up

    

         WARNING!   Ensure  that  both  shut-off  valves  are  open  before  starting  the 

 compressor!

 

  Check that the safety and protection devices (pressure switch, motor protection, electrical con

-

tact protection measures, etc.) are functioning properly.

  Switch on the compressor and let it run for at least 10 minutes.
  Check the 

oil level

 : The oil must be visible in the sight glass.

 

        ATTENTION!  If larger quantities of oil have to be topped up, there is a risk of oil 

impact effects. If this is the case, check the oil return!

6.7  Avoiding liquid sluggings

                    ATTENTION! Slugging  can  result  in  damage  to  the  compressor  and  cause 

  

 

refrigerant to leak.

To prevent slugging:

  The complete refrigeration plant must be properly designed.
  All components must be compatibly rated with each other with regard to output (particularly the 

evaporator and expansion valves).

  Suction gas superheating at the compressor input 

should be min. 7 - 10

 K (check the setting of 

the expansion valve).

  The system must reach a state of equilibrium. 
   Particularly in critical systems (e.g. several evaporator points), measures such as the use of liquid 

traps, solenoid valve in the liquid line, etc. are recommended. 

 

There should be no movement of coolant whatsoever while the compressor is at a 
 standstill.

Содержание HG Series

Страница 1: ...ering for a better world GEA Refrigeration Technologies Bock Compressor HGX22P R410A Assembly instructions HGX22P 125 4 R410A HGX22P 125 4 S R410A HGX22P 160 4 S R410A HGX22P 190 4 R410A HGX22P 190 4...

Страница 2: ...the compressor can result in serious or fatal injury Observe the safety instructions contained in these instructions These instructions must be passed onto the end customer along with the unit in whic...

Страница 3: ...on for contactor and motor contactor selection 5 2 Connection of the driving motor 5 3 Circuit diagram direct start 230 V 400 V Y 5 4 Electronic trigger unit MP 10 5 5 Connecting of the trigger unit M...

Страница 4: ...ential dangers WARNING Refrigerating compressors are pressurised machines and therefore require particular caution and care in handling Risk of burns Depending on the operating conditions surface temp...

Страница 5: ...efrigerating compressor named in the title is intended for installing in a machine within the EU according to the EU Directives 2006 42 EC Machinery Directive 97 23 EC Pressure Equipment Directive and...

Страница 6: ...brication Suction gas cooled drive motor Compact dimensions quiet running high efficiency Fig 1 2 1 Short description Fig 2 Oil sight glass Valve plate Cylinder cover Discharge shut off valve Oil pump...

Страница 7: ...f poles Swept volume Number of cylinders Size Ester oil filling Series IP66 1 Type designation 2 Machine number 3 maximum operating current 4 Starting current rotor blocked 5 ND LP max admissible oper...

Страница 8: ...Avoid continuous operation near the threshold For operation with frequency converter The maximum current and power consumption must not be exceeded In the case of operation above the mains frequency...

Страница 9: ...application range Supplementary cooling or reduced suction gas temperature Motor version S more powerful motor Evaporation temperature C Condensing temperature C Suction gas temperature C Max permiss...

Страница 10: ...standart millimetre and inch dimansions can be used The connection diameters of the shut off valves are rated for maximum compressor output The actual required pipe cross section must be matched to th...

Страница 11: ...sure a proper oil return Keep pressure losses to an absolute minimum Fig 10 Rigid fixed point As short as possible 4 4 Laying suction and pressure lines INFO Proper layout of the suction and pressure...

Страница 12: ...lockwise Fig 11 Fig 12 Pipe connection Pipe connection 4 6 Operating mode of the lockable service connections Fig 13 Opening the shut off valve Spindle turn to the left counter clockwise as far as it...

Страница 13: ...nly carry out work when the electrical system is disconnected from the power supply INFO Connect the compressor motor in accordance with the circuit diagram see inside of terminal box Use suitable cab...

Страница 14: ...V Y Fig 15 R1 Cold conductor PTC sensor motor winding R2 Thermal protection thermostat PTC sensor F1 Motor safety switches F2 Control power circuit fuse F3 Safety chain high low pressure monitoring B1...

Страница 15: ...voltage switch M1 Compressor motor K1 Mains contactor MP10 Trigger unit MP 10 E1 Oil sump heater X3 Terminal block in the terminal box A1 Alarm motor protection A2 Temperature rise R1 R2 A3 Alarm high...

Страница 16: ...the H3 LED green after the power supply is applied In the case of excess temperature in the motor winding the unit switches off the compressor and the H1 LED lights red The hot gas side of the compres...

Страница 17: ...operational when the H3 LED green lights 5 6 Function test of the trigger unit MP 10 Pos Procedure LED H1 LED H2 LED H3 red red green 1 Interrupt power supply L1 or S1 OFF OFF OFF Release the motor t...

Страница 18: ...gerant with the testing medium as this could cause the ignition limit to shift into the critical range 6 4 Evacuation First evacuate the system and then include the compressor in the evacuation proces...

Страница 19: ...fore starting the compressor Check that the safety and protection devices pressure switch motor protection electrical con tact protection measures etc are functioning properly Switch on the compressor...

Страница 20: ...mpressor Release switch on lock 6 8 Connection of oil level regulator 6 Commissioning The connection O is provided for installing an oil level regulator A corresponding adapter must be obtained from t...

Страница 21: ...standard oil types Recommended alternatives HFKW R410A Fuchs Reniso Triton SE 55 Fuchs SEZ 32 ICI Emkarate RL 46 S Mobil Arctic AL 46 Shell Clavus R 46 7 Maintenance 7 6 Decommissioning Close the shut...

Страница 22: ...A 16 5 19 8 24 6 14 2 8 4 121 70 81 HGX22P 190 4 S R410A 29 3 16 9 9 7 134 77 84 Type 1 2 3 2 4 220 240 V 380 420 V Y 3 50 Hz 265 290 V 440 480 V Y 3 60 Hz Tolerance 10 relative to the mean value of t...

Страница 23: ...R410A Dimensions in only for HGX22P 125 4 R410A Massensch Centre of g Centre de g H D1 SV A1 223 328 361 109 ca 505 470 ca 20 J DV F L1 E B A O K B1 115 88 198 264 ca 240 4x 12 ca 310 4 5 6 7 4 5 6 7...

Страница 24: ...410A complies with the basic requirements of Appendix II 1B of the Machinery Directive 2006 42 EC The following harmonised standards have been applied EN ISO 12100 1 EN ISO 12100 2 EN 12693 EN 349 A p...

Страница 25: ...den Sie sich bitte an unsere Anwendungstechnik oder a K ltefachgro handel bzw unsere Vertretung Das Bock Serviceteam erreichen Sie direkt u 49 7022 9454 0 via e mail mail bock de oder im Internet www...

Страница 26: ...han 50 countries Founded in 1881 the company is one of the largest providers of innovative equipment and process technology GEA Group is listed in the STOXX Europe 600 Index 96166 05 2012 DGbFEI GEA G...

Отзывы: