GRASSO SYSTEM CONTROL
Chap. 1 - 8 638660E_chapter1.doc 01.200
4
/
1
Unloaded start
Motor feedback
Auto start dly
Unloaded start:
Remaining time for unloaded start in secs
Motor feedback: Remaining time for motor running feedback signal from
compressor drive motor starter
<<
Actual values 01 >>
Auto start dly:
Remaining time for automatic start delay in secs
Step time
Limit time
Run hours
Step time:
Remaining time for next capacity step in secs
Limit time:
Remaining time for the capacity limitation in secs
Run hours:
Number of operating hours
<<
Actual values 01
1.2.3.2
Control settings menu
10 Control settings
Set Point 1
Set Point 2
Active SP
Set Point 1:
First Set Point for the controlled parameter °C
Set Point 2:
Second Set Point for the controlled parameter °C
Active SP:
Active Set Point in °C
<<
Control 01
>>
The active set point value is displayed. 2 different set point values can be
entered via the display. The switchover takes place due to a potential free
contact or due to MPI/Profibus-DP communication.
Furthermore, an external set point (analogue input or MPI/Profibus-DP
signal) can be activated. This switchover takes place due to the selected
operation mode in the menu “Operating mode”
.
Active SP
Neutral zone
Prop zone
Active SP:
Active set point in °C
Neutral zone:
Neutral zone of the automatic capacity regulation in K
Prop zone:
Proportional zone of the automatic capacity regulation in
<<
Control 01
>>
K
Step times
min |
max
Cap inc
|
Cap dec
|
Cap inc min:
Minimal step time for increasing the capacity in secs
Cap inc max:
Maximal step time for increasing the capacity in secs
Cap dec min:
Minimal step time for decreasing the capacity in secs
<<
Control 01
>>
Cap dec max:
Maximal step time for decreasing the capacity in secs
Auto start dly
Pump down
Stop pressure
Auto start dly:
Time for automatic start delay in secs
Pump down:
Selection between “with” or “without” pump down
Stop pressure:
If pump down is activated, the compressor does not stop
<<
Control 01
>>
before the suction pressure reaches this value in bar (a)
Boost press
Cor P-zone
Derative fact
Boost press:
Booster pressure in bar (a) .
Cor P-zone:
Correction value of the proportional zone in K for
decreasing the capacity (+ towards the set point / - away
<<
Control 01
from set point)
Derative fact:
Maximum temperature difference in K allowed within 5
seconds otherwise the capacity will be changed
immediately (0 = derative function deactivated)
Содержание Grasso
Страница 4: ......
Страница 8: ......
Страница 9: ......
Страница 10: ......
Страница 12: ......
Страница 32: ......
Страница 33: ......
Страница 34: ......
Страница 73: ......
Страница 74: ......
Страница 76: ......
Страница 84: ......
Страница 85: ......
Страница 86: ......
Страница 88: ......
Страница 95: ......
Страница 96: ......
Страница 98: ......
Страница 109: ......
Страница 110: ......
Страница 112: ......
Страница 134: ......
Страница 135: ......
Страница 136: ......
Страница 138: ......
Страница 147: ......
Страница 148: ......
Страница 154: ......
Страница 155: ......
Страница 156: ......
Страница 164: ......
Страница 165: ...02 04 Master_Backpage doc 1 ...
Страница 166: ......