Grasso
Refrigeration Division
GRASSO SYSTEM CONTROL
01.2003/0
638660E_chapter6.doc
Kap.6 - 7
Display message / Explanation
Possible cause of the alarm
Alarm clearance
The external temperature is too
low.
Remove cause of low external
temperature in the refrigeration plant.
025 Alarm
External temperature
too low
‘Text low alarm’ limit is set too
high.
Change ‘Text low alarm’ limit to a
suitable value.
The sensor has not been correctly
calibrated in the configuration
menu.
Enter the correct calibration value.
This alarm is activated if the external
temperature falls below the ’Text
low alarm’ limit value.
The sensor is defective.
Replace the sensor.
MPI / Profibus-DP cable broken or
plug-in connector defective.
Replace the defective parts.
030 Alarm
MPI / Profibus-DP
network comm.
failure
The master PLC operation mode
state is ’STOP’.
Change the PLC operation mode into
‘RUN’.
The ‘Life-bit’ of the slave is not
returned by the master.
Check the master PLC program.
This alarm is activated at the slave
GSC if an operation mode has been
activated, where data exchange via
MPI or Profibus-DP is activated, and
the slave GSC is not connected to
the master.
Wrong selection of the ’Netw fault’
parameter in the operating mode
menu.
Select the correct setting for the
’Netw fault’ parameter.
The terminal connections have
become loose or a wire is broken.
Check the terminal connections for
tightness and continuity of wiring.
031 Alarm
PLC power supply
interrupted
Wrong selection of the ‘Power
return’ parameter in the operating
mode menu.
Select the correct setting for the
’Power return’ parameter.
This alarm is activated if the PLC
power supply has been interrupted.
The configuration is invalid.
Check the parameter ‘Refrigerant’ in
the configuration menu.
032 Alarm
Refrigerant data
not found. Please
select other refr.
This alarm is activated if during the
configuration a refrigerant has been
selected that is not available on the
EPROM.
The selected refrigerant is not
available on the EPROM.
If the correct refrigerant has been
selected and this alarm occurs, where
the PLC shows no other failures, the
EPROM has to be exchanged.
The terminal connections have
become loose or a wire is broken.
Check the terminal connections for
tightness and continuity of wiring.
049 Alarm
(01)
Wire failure
crankcase pressure
There is a short circuit in the sensor
wiring.
Check where the short circuit has
occured and rectify.
The sensor is defective.
Replace the sensor.
The GSC has detected a loose wire
or short circuit in the crankcase
pressure sensor.
The analogue input module
defective.
Replace the analogue input module.
Содержание Grasso
Страница 4: ......
Страница 8: ......
Страница 9: ......
Страница 10: ......
Страница 12: ......
Страница 32: ......
Страница 33: ......
Страница 34: ......
Страница 73: ......
Страница 74: ......
Страница 76: ......
Страница 84: ......
Страница 85: ......
Страница 86: ......
Страница 88: ......
Страница 95: ......
Страница 96: ......
Страница 98: ......
Страница 109: ......
Страница 110: ......
Страница 112: ......
Страница 134: ......
Страница 135: ......
Страница 136: ......
Страница 138: ......
Страница 147: ......
Страница 148: ......
Страница 154: ......
Страница 155: ......
Страница 156: ......
Страница 164: ......
Страница 165: ...02 04 Master_Backpage doc 1 ...
Страница 166: ......