GRASSO SYSTEM CONTROL
01.2003/0
638660E_chapter6.doc
Kap.6 - 19
Warning message
Possible cause
Warning clearance
Suction pressure is too low.
Remove the cause for low suction
pressure in the refrigerating plant.
105 Warning
(01)
Low suction
pressure
‘Psuc low alarm’ plus ‘Low warning’
set too high.
Change ‘Psuc low alarm‘ and ‘Low
warning‘ limits to suitable values.
The sensor has not been correctly
calibrated in the configuration
menu.
Enter the correct calibration value.
This warning is activated if the
suction pressure is less than ‘Psuc
low alarm’ plus ‘Low warning’ limit
values.
The sensor is defective.
Replace the sensor.
The suction pressure is too high.
Remove the reason for the high
suction pressure in the refrigerating
plant.
106 Warning
(01)
High suction
pressure
‘Psuc hi alarm’ minus ‘High
warning’ set too high.
Change ‘Psuc hi alarm‘ and ‘High
warning‘ limits to suitable values.
The sensor has not been correctly
calibrated in the configuration
menu.
Enter the correct calibration value.
This warning is activated if the
suction pressure is higher than the
‘Psuc hi alarm’ minus ‘High warning’
limit values.
The sensor is defective.
Replace the sensor.
The discharge pressure is too high.
Remove the reason for the high
discharge pressure in the
refrigerating plant.
107 Warning
(01)
High discharge
pressure
‘Pdis hi alarm’ minus ‘High
warning’ set too high.
Change ‘Pdis hi alarm‘ and ‘High
warning‘ limits to suitable values.
The sensor has not been correctly
calibrated in the configuration
menu.
Enter the correct calibration value.
This warning is activated if the
discharge pressure is higher than the
‘Pdis hi alarm’ minus ‘High warning’
limit values.
The sensor is defective.
Replace the sensor.
The intermediate pressure is too
high.
Remove the reason for the high
intermediate pressure in the
refrigerating plant.
108 Warning
(01)
High intermediate
pressure
‘Pint hi alarm’ minus ‘High warning’
set too high.
Change ‘Pint hi alarm‘ and ‘High
warning‘ limits to suitable values.
The sensor has not been correctly
calibrated in the configuration
menu.
Enter the correct calibration value.
This warning is activated if the
intermediate pressure is higher than
the ‘Pint hi alarm’ minus ‘High
warning’ limit values.
The sensor is defective.
Replace the sensor.
The oil differential pressure is too
low.
Remove cause of low oil
differential pressure at the
compressor.
109 Warning
(01)
Low oil
differential pressure
This warning is activated if the oil
difference between the oil pressure
and crankcase pressure or suction
pressure (only if no crankcase
pressure is available) is less than the
’dPoil low alarm’ plus ‘Low warning’
limit values.
‘dPoil low alarm’ plus ‘Low
warning’ set too high.
Change ‘dPoil low alarm’ and ‘Low
warning’ limits to a suitable values.
Содержание Grasso
Страница 4: ......
Страница 8: ......
Страница 9: ......
Страница 10: ......
Страница 12: ......
Страница 32: ......
Страница 33: ......
Страница 34: ......
Страница 73: ......
Страница 74: ......
Страница 76: ......
Страница 84: ......
Страница 85: ......
Страница 86: ......
Страница 88: ......
Страница 95: ......
Страница 96: ......
Страница 98: ......
Страница 109: ......
Страница 110: ......
Страница 112: ......
Страница 134: ......
Страница 135: ......
Страница 136: ......
Страница 138: ......
Страница 147: ......
Страница 148: ......
Страница 154: ......
Страница 155: ......
Страница 156: ......
Страница 164: ......
Страница 165: ...02 04 Master_Backpage doc 1 ...
Страница 166: ......