Display message / Explanation
Possible cause of the alarm
Alarm clearance
‘Pump down time’ too short.
Increase the ‘Pump down time’ in the
time values menu to a suitable value.
096 Alarm
(01)
Pump down time
elapsed. Stop pressure
not reached
‘Stop pressure’ value set too low.
Change the ‘Stop pressure’ value in
the control menu to a suitable value.
This alarm is activated if the stop
pressure is not reached within the
maximum time allowed.
Wrong selection of the
‘Pump down’ parameter in the
control menu.
Select the correct setting for the
‘Pump down’ parameter.
6.4
Description and diagnosis of warning messages
Warning message
Possible cause
Warning clearance
The external temperature is too
low.
Remove the cause of low external
temperature in the refrigeration
plant.
037 Warning
Low external
temperature
’Text low alarm’ plus ’Low warning’
set too high.
Change ’Text low alarm’ and ’Low
warning’ limits to suitable values.
The sensor has not been correctly
calibrated in the configuration
menu.
Enter the correct calibration value.
This warning is activated if the
external temperature is less than
’Text low alarm’ plus ’Low warning’
limit values.
The sensor is defective.
Replace the sensor.
The terminal connections have
become loose or a wire is broken.
Check the terminal connections for
tightness and continuity of wiring.
041 Warning
PLC power supply
interrupted
Wrong selection of the ‘Power
return’ parameter in the operating
mode menu.
Select the correct setting for the
’Power return’ parameter.
This warning is activated if the PLC
power supply has been interrupted.
The battery is empty.
Replace the battery.
042 Warning
Replace PLC
battery
This warning is activated if the PLC
battery is empty. The ’BATF’ LED on
the GSC also lights up.
043 Warning
PLC operation
mode changed
After ending of the saving
procedure, which can be activated
by pressing ‘save’ in the
configuration menu, this warning is
activated for 2 seconds only.
No action needed.
This warning is activated if the PLC
operation mode has been changed.
Содержание Grasso
Страница 4: ......
Страница 8: ......
Страница 9: ......
Страница 10: ......
Страница 12: ......
Страница 32: ......
Страница 33: ......
Страница 34: ......
Страница 73: ......
Страница 74: ......
Страница 76: ......
Страница 84: ......
Страница 85: ......
Страница 86: ......
Страница 88: ......
Страница 95: ......
Страница 96: ......
Страница 98: ......
Страница 109: ......
Страница 110: ......
Страница 112: ......
Страница 134: ......
Страница 135: ......
Страница 136: ......
Страница 138: ......
Страница 147: ......
Страница 148: ......
Страница 154: ......
Страница 155: ......
Страница 156: ......
Страница 164: ......
Страница 165: ...02 04 Master_Backpage doc 1 ...
Страница 166: ......