Accessories for Drawout Breakers

Auxiliary Switch 

(Field installable kit available)

The auxiliary switch is used for indication of breaker main
contact position. It is available on manually and electrically

operated breakers in either
a 4-stage or 7-stage config-
uration. The 4-stage switch
yields 3NO and 3NC con-
tacts while the 7-stage
switch yields 6NO and 6NC
contacts. Normally open
(NO) contacts follow the

breaker primary contact position while normally closed
(NC) contacts operate opposite the breaker primary con-
tacts. All auxiliary switch contacts feature rugged double-
break construction. Refer to breaker wiring diagram
10057403P1 for contact configurations and secondary dis-
connect terminations. Ratings of the auxiliary switch con-
tacts are shown in Table 7.1.

Table 7.1

Auxiliary switch ratings and contact operation

Table 7.2

Table 7.3

Bell Alarm with/without Lockout 

(Field installable kit available)

The bell alarm device is provided with two C-form contacts
— each C-form contact is
1NO and 1NC contact with 
a common connection. The
bell alarm device operates
whenever the breaker trips
due to a protective function
of the trip unit. It can be
used to provide remote indi-

Field installable auxiliary switch kit catalog numbers

Auxiliary switch

WP-08 / 16 / 20

WP-32 / 40

WP-50

Four stage

WPAUXSF4STG

WPAUXLF4STG

WPAUXXF4STG

Seven stage

WPAUXSF7STG

WPAUXLF7STG

WPAUXXF7STG

Auxiliary switch contact operation

Breaker primary contacts

“a”-contact (NO)

“b”-contact (NC)

Open or tripped

Open

Closed

Closed

Closed

Open

Auxiliary Switch Ratings 

Rating (Amperes)

Control Voltage

Non-inductive

Inductive

24

15

10

DC

125

10

5

250

5

5

AC - 60Hz

120

15

15

240

10

10

20A continuous rating of switch limited to 15A continuous 
rating of #16AWG wire on drawout breakers

cation of a fault trip and/or disable electrical operation of
breakers that may have automatic control.

For Power+™ and MicroVersaTrip Plus™ trip units, the bell
alarm will operate for overload, short circuit and ground
fault trips. For MicroVersaTrip PM™ trip units, the bell
alarm will operate for the same overcurrent trips plus any 
of the protective relay trips that are enabled in the trip unit.
Tripping via the manual trip button, shunt trip, undervoltage
device or open fuse lockout will not operate the bell alarm.

The bell alarm can be furnished with a mechanical lockout
feature that will prevent the breaker from being manually
closed until the lockout is reset. Reset of the contacts and lock-
out feature is accomplished by pushing the yellow “reset” but-
ton on the breaker escutcheon. The reset button also serves as
a target indicator that the bell alarm has been operated.
Ratings of the bell alarm contacts are shown in Table 7.4.

Table 7.4 Bell alarm contact ratings

Table 7.5

Electrical Lockout 

(Field installable kit available)

The electrical lockout device provides a means to electrically
enable or disable manual closing of a circuit breaker. This
device must be energized prior to attempting to manually
close the breaker. Once the breaker is closed, loss of voltage
will not trip the breaker. A manual bypass interlock is pro-
vided for initial startup. Refer to the undervoltage device for
ratings and coil characteristics. (Note: Interlocking of elec-
trically operated breakers does not require an electrical
lockout device.)

Table 7.6

Field installable electrical lockout kit catalog numbers

Control voltage

WP-08 / 16 / 20

WP-32 /  40 / 50

120Vac 50/60Hz

WPELSF56120

WPELLF56120

240 Vac 50/60Hz

WPELSF56240

WPELLF56240

24Vdc

WPELSFDC024

WPELLFDC024

48Vdc

WPELSFDC048

WPELLFDC048

110Vdc

WPELSFDC110

WPELLFDC110

125Vdc

WPELSFDC125

WPELLFDC125

250Vdc

WPELSFDC250

WPELLFDC250

Field installable bell alarm kit catalog numbers

(Kit provides choice of with or without lockout)

WP-08 / 16 / 20

WP-32 / 40 / 50

WPBASF

WPBALF

Bell Alarm Contact Ratings

AC Ratings

DC Ratings

6A @ 240Vac

0.5A @ 125Vdc

0.25A @ 250Vdc

Содержание WavePro LVPCB

Страница 1: ...WaveProTM Low Voltage Power Circuit Breakers Application Guide The Ultimate Assurance In Uptime And Reliability Now with 100kAIC ratings...

Страница 2: ...Plus and PM 17 Trip Units MicroVersaTrip Plus 18 Trip Characteristics MicroVersaTrip Plus and PM 19 Trip Characteristics Power MicroVersaTrip Plus and PM 21 Trip Units MicroVersaTrip PM 23 MicroVersaT...

Страница 3: ...rings Operation of the breaker can be accomplished through manual OPEN CLOSE buttons on the escutcheon The escutcheon also includes indicators for closing spring status main contact status and breaker...

Страница 4: ...remote close accessory CLOSE and TRIP push button covers sealable remote charge indicator switch 8 Sealable door over the trip unit trip settings can be viewed but not changed 9 Easy access to key bre...

Страница 5: ...S 50 5000 85 85 85 WPX 50 5000 100 100 100 WPS 08 800 30 42 30 WPH 08 800 42 50 42 WPX 08 800 65 65 65 240 WPS 16 1600 50 65 50 WPH 16 1600 65 65 65 254 WPS 20 2000 65 65 65 WPS 32 3200 65 85 65 WPH 3...

Страница 6: ...ures 5 Padlocking devices A Supplied on all breakers the padlocking device allows up to three padlocks 1 4 to 3 8 diameter shank to be installed to keep the breaker mechanically trip free B A drawout...

Страница 7: ...5 Features Characteristics cont 2 1A 9 3 1B 7 5A 12 6 11 10 8 9 4 5C...

Страница 8: ...ing the ability to block automatic recharging of the springs if required by the breaker application The anti pump feature in the closing circuit provides one closing operation of the breaker for each...

Страница 9: ...s that may have automatic control For Power and MicroVersaTrip Plus trip units the bell alarm will operate for overload short circuit and ground fault trips For MicroVersaTrip PM trip units the bell a...

Страница 10: ...lling and removing the WavePro draw out breakers It attaches to the breaker to provide stability when lifting the breaker from its drawout rails Pickup points on the breaker and lifting tool are WP 08...

Страница 11: ...Table 9 1 Field installable Remote Charge Indicator Switch kit catalog numbers Remote Close Accessory with One Shot Electronic Close Circuit Field installable kit available The remote close accessory...

Страница 12: ...not require the use of a shunt trip The shunt trip coil is rated for intermittent duty and is supplied with an auxiliary switch contact that automatically removes control power following a breaker tri...

Страница 13: ...p thus preventing potential nuisance tripping due to momentary loss of volt age The time delay unit is 11 Accessories for Drawout Breakers cont mounted externally to the breaker It is rated 125Vdc 250...

Страница 14: ...l DL1616B which may be pur chased commercially Long time pickup The long time pickup indicator moves through two transitions As the current in any phase reaches 95 of its setpoint the LTPU LED begins...

Страница 15: ...uator trip signal from the microprocessor to the trip actuator The trip actuator is a low energy positive action tripping device The low level trip signal counteracts the strength of the actuator s pe...

Страница 16: ...reaker will withstand for short peri ods of time to allow downstream devices to clear faults without tripping the breaker Settings are adjustable in increments of the breaker current setting C See Tab...

Страница 17: ...es not exceed 1200 amps There are three ground fault delay bands of 1 MIN 2 INT 3 MAX ranging from 100 ms to 350 ms The I2 t function adds an I2 t slope to the square corner of the ground fault time c...

Страница 18: ...trips initiated by the trip unit will cause the bell alarm if so equipped to operate Reset of the bell alarm contacts and the mechanical lockout if provided is by way of the reset button on the breake...

Страница 19: ...life lithium batteries provide program ming and display power to the trip unit s LCD on com mand With the breaker disconnected from the source and load the trip unit can be removed from the breaker an...

Страница 20: ...change state whenever the trip actuator causes the breaker to open The bell alarm is not activated by any other manual or electrical tripping means Standard And Optional Protective Functions Standard...

Страница 21: ...s current setting or value of LT Long time delay Instantaneous Function Standard All WavePro breakers are available with standard adjustable instantaneous trip function The instantaneous trip point es...

Страница 22: ...ings such that the maximum setting does not exceed 1200 amps There are three ground fault delay bands of 1 MIN 2 INT 3 MAX ranging from 100 ms to 350 ms The I2 t function modifies the square corner of...

Страница 23: ...2 0 3 0 5 0 7 0 20 25 30 35 WPX 08 1 5 2 0 3 0 5 0 9 0 10 0 13 0 15 0 40 45 50 60 WPF 08 7 0 9 0 10 0 WPS 16 WPH 16 MVT Plus PM MVT Plus PM WPF 16 1 5 thru 15 0 in steps of 0 20 thru 0 60 in steps of...

Страница 24: ...ckup protection If a fault occurs between two breakers equipped with zone selective interlocking the upstream breaker would clear the fault on the minimum delay band because it receives no interlock s...

Страница 25: ...yed without the use of the trip unit internal batteries similar to the operation of the MicroVersaTrip PM trip unit Communications Output The communications network uses a pair of shielded twisted wir...

Страница 26: ...ve relaying functions are selected any combi nation of the following protective relays can be enabled All relay functions combine both an adjustable setpoint and an adjustable discrete not inverse tim...

Страница 27: ...rs use the same programming keypads All functions ordered are selectable and displayed Programming display and keypad Function Selects the mode of the display Setup Metering or Status Select Chooses t...

Страница 28: ...ombinations for MicroVersaTrip Plus PM Breaker Frame Rating Sensor Rating Available Rating Plugs Amps CT In 800 150 60 80 100 125 150 800 400 150 200 225 250 300 400 800 1600 800 300 400 450 500 600 7...

Страница 29: ...1200 TR20C1200GF TR20C1200GFD TR20B1200 1500 N A N A N A TR20B1500 1600 TR20C1600 TR20C1600GF TR20C1600GFD TR20B1600 2000 TR20C2000 TR20C2000GF TR20C2000GFD TR20B2000 1200 TR32C1200 TR32C1200GF TR32C1...

Страница 30: ...lass L fuse J 7 1600A Class L fuse K 8 2000A Class L fuse L 9 2500A Silver L fuse M 800A Welder limiter N 1600A Welder limiter Q 2000A Welder limiter R 1000A Welder limiter Z Frame Sensor Code See Not...

Страница 31: ...DC P 125v DC Q 250v DC R 240v 60Hz T 240v 50Hz W Requires min 4 stage auxiliary switch and shunt trip Shunt Trip 1 Code none X 120VAC 60Hz 1 208VAC 60Hz 2 240VAC 60Hz 3 70VAC 60Hz 4 120VAC 50Hz 5 208V...

Страница 32: ...25WATT FOR 240VAC WAVEPRO CIRCUIT BREAKER ELEC MAN OPERATED OPTIONAL SECOND SHUNTTRIP DEVICE MOMENTARY TC 2 Y MB FUSE X FUSE 2 C14 1 TRIP AUX 13 13C L C5 Z W1 W2 SHOT ONE S OS 2 1 V RES NOTE 10 Y Y TC...

Страница 33: ...S 20 WPS 32 WPS 40 WPS 50 FRAMES ONLY A28 A29 31 47 T ZSI IN A30 A31 30 46 T ZSI OUT MVT PLUS PM PM READY ONL Y INTERLOCKING INPUT OUTPUT ZONE SELECTIVE TRIP UNIT A24 A25 T NS 49 50 INPUT NEUTRAL SENS...

Страница 34: ...ied to accept lower rated fuses WPF 16 breakers equipped with 2000A and lower fuses cannot be upgraded to 2500A fuses The maximum trip rating for a WPF 16 breaker is 1200A when furnished with other th...

Страница 35: ...ower circuit breakers at altitudes greater than 6 600 feet their continuous current rating must be modified because a higher temperature use will be experi enced for a given current rating The voltage...

Страница 36: ...34 Time Current Curves...

Страница 37: ...Time Current Curves cont 35...

Страница 38: ...36 Time Current Curves cont...

Страница 39: ...and breaking rated current at rated maximum voltage and 2 additional no load mechanical on off operations per Table 36 1 Table 36 1 Endurance requirements for low voltage AC power circuit breakers Sh...

Страница 40: ...hat it is immune to nuisance trips or improper operation when nearby walkie talkies are used 6 Wiggins Immunity Tests are performed to ensure the breaker will not nuisance trip when exposed to a high...

Страница 41: ...condary disconnect points All breaker control circuits as well as inputs and outputs for the trip unit shall be wired through the sec ondary disconnects Secondary disconnect points shall be self align...

Страница 42: ...able I2 t ramp f SELECT ONE OF THE FOLLOWING IF GROUND FAULT PROTECTION IS REQUIRED 1 Adjustable ground fault pickup and time delay with three delay bands and switchable I2 t ramp 2 Defeatable ground...

Страница 43: ...lay with three delay bands and switchable I2 t ramp and or adjustable instanta neous pickup f SELECT ONE OF THE FOLLOWING IF GROUND FAULT PROTECTION IS REQUIRED 1 Adjustable ground fault pickup and ti...

Страница 44: ...imagination at work GE Consumer Industrial 41 Woodford Avenue Plainville CT 06062 www GEindustrial com 2004 General Electric Company DET 167C 0904 BL...

Отзывы: