MicroVersaTrip PM™  Metering and Relaying

Metering

When the metering function is selected, a number of stan-
dard metering parameters can be viewed on the LCD dis-
play. All of these values are communicated to the POWER
LEADER™ Power Management System. The accuracy of the
metering functions is constrained by the physical size of the
current sensors. Consequently, all metering functions are
designed for load management decisions, and are not a 
substitute for utility revenue metering equipment.
• Current: 

MicroVersaTrip Plus™ and PM™, provide 

metering of individual phase currents. The user can 
view each phase current individually. Current displays
automatically shift from amps to kiloamps above 999
amps. The minimum current display resolution is in
tenths of an amp (e.g., 51.2 A).

• Voltage: 

The metering display of four wire systems can

read both line-to-neutral and line-to-line voltages for each
phase. The smallest resolution of the voltage display is
one volt (e.g., 277V, or 276V).

• Energy: 

The energy display indicates the amount of real

power that has passed through the breaker. The display
has three-digit resolution, and automatically scales the dis-
play from kWh to MWh to GWh. Normal power flow can
be selected as either line-load or load-line in the setup
mode. Once normal flow is configured, energy values will
accumulate in the positive direction. For certain applica-
tions where power may flow in either direction, such as tie
breakers, energy may display a negative value.

• Real power: 

Real power in units of kW or MW, can be

shown on command on the LCD display.

• Volt-amperes (or total power): 

“Total power” or volt-amperes

in units of kVA or MVA can be viewed on command on
the LCD display.

• Demand: 

Demand in units of kW or MW can be displayed.

The monitoring time period can be varied from 5 to 60
minutes, in increments of 5 minutes. The display provides
a rolling average of power over the scheduled time inter-
val.

• Peak demand: 

Peak demand in units of kW or MW can be

displayed. This value indicates the highest power demand
reached since the start of demand measurements, or
since reset. The peak demand value can be reset to the
present demand via the keypad.

Protective Relaying

When protective relaying functions are selected, any combi-
nation of the following protective relays can be enabled. All
relay functions combine both an adjustable setpoint and an
adjustable discrete (not inverse) time delay. All time delays
are adjustable from 1 to 15 seconds in increments of 1 sec-
ond. All tripping is performed through the trip unit. Any
protective relay trip will operate the bell alarm accessory if
the breaker is so equipped.

• Undervoltage: 

Undervoltage protection may be set from

50% to 90% of the true rms nominal voltage in incre-
ments of 1%.

• Overvoltage: 

Overvoltage protection may be set from 110%

to 150% of the true rms nominal voltage in increments of
1%.

• Voltage unbalance: 

Voltage-unbalance protection compares

the lowest or highest phase voltage with the other two,
and initiates a trip if the difference exceeds the setpoint.
True rms voltages are computed for each phase. The
range of trip settings varies from 10% to 50% in incre-
ments of 1%.

• Current unbalance: 

Current-unbalance protection com-

pares the true rms current in either the highest or lowest
phase with the true rms current in the other two phases.
A trip is initiated if the difference exceeds the setpoint.
The range of trip settings varies from 10% to 50% in
increments of 1%.

• Power reversal: 

WavePro™ breakers may be set so that

“positive” power flow can be in either direction (i.e., from
line to load, or vice versa). Reverse power protection is set
in units of kW. Reverse power setpoints vary from 10 kW
to 990 kW in increments of 10 kW.

• Enable/disable relays: 

To disable any of the protective relay

functions, set the time delay for that function to OFF.
Setting the time delay to any discrete value enables the
protective function.

Table 24.1 Trip Unit Metering Display Accuracy

Value

Breaker Full 

System Full 

Scale Scale 

Accuracy 

Accuracy 

Current, rms-A, kA

±2.0%

±2.0%

Voltage, rms-V
Phase-Phase, Phase-Neutral

N/A

±1.5%

Energy-kWh, MWh, GWh

N/A

±3.5%

Demand-kW, MW

N/A

±3.5%

Peak demand-kW, MW

N/A

±3.5%

Real power-kW, MW

N/A

±3.5%

Total power-kVA, MVA

N/A

±3.5%

Frequency

N/A

±1Hz

Time delay

N/A

±1 sec

Includes trip unit, breaker, current sensors and rating plug. Accuracy

is based on loading range of 20% to 100% of breaker current sensor

rating.

Includes trip unit, breaker, current sensors, rating plug, plus Voltage

Module (potential transformer, voltage conditioner). Accuracy is

based on loading range of 20% to 100% of breaker current sensor

rating.

Содержание WavePro LVPCB

Страница 1: ...WaveProTM Low Voltage Power Circuit Breakers Application Guide The Ultimate Assurance In Uptime And Reliability Now with 100kAIC ratings...

Страница 2: ...Plus and PM 17 Trip Units MicroVersaTrip Plus 18 Trip Characteristics MicroVersaTrip Plus and PM 19 Trip Characteristics Power MicroVersaTrip Plus and PM 21 Trip Units MicroVersaTrip PM 23 MicroVersaT...

Страница 3: ...rings Operation of the breaker can be accomplished through manual OPEN CLOSE buttons on the escutcheon The escutcheon also includes indicators for closing spring status main contact status and breaker...

Страница 4: ...remote close accessory CLOSE and TRIP push button covers sealable remote charge indicator switch 8 Sealable door over the trip unit trip settings can be viewed but not changed 9 Easy access to key bre...

Страница 5: ...S 50 5000 85 85 85 WPX 50 5000 100 100 100 WPS 08 800 30 42 30 WPH 08 800 42 50 42 WPX 08 800 65 65 65 240 WPS 16 1600 50 65 50 WPH 16 1600 65 65 65 254 WPS 20 2000 65 65 65 WPS 32 3200 65 85 65 WPH 3...

Страница 6: ...ures 5 Padlocking devices A Supplied on all breakers the padlocking device allows up to three padlocks 1 4 to 3 8 diameter shank to be installed to keep the breaker mechanically trip free B A drawout...

Страница 7: ...5 Features Characteristics cont 2 1A 9 3 1B 7 5A 12 6 11 10 8 9 4 5C...

Страница 8: ...ing the ability to block automatic recharging of the springs if required by the breaker application The anti pump feature in the closing circuit provides one closing operation of the breaker for each...

Страница 9: ...s that may have automatic control For Power and MicroVersaTrip Plus trip units the bell alarm will operate for overload short circuit and ground fault trips For MicroVersaTrip PM trip units the bell a...

Страница 10: ...lling and removing the WavePro draw out breakers It attaches to the breaker to provide stability when lifting the breaker from its drawout rails Pickup points on the breaker and lifting tool are WP 08...

Страница 11: ...Table 9 1 Field installable Remote Charge Indicator Switch kit catalog numbers Remote Close Accessory with One Shot Electronic Close Circuit Field installable kit available The remote close accessory...

Страница 12: ...not require the use of a shunt trip The shunt trip coil is rated for intermittent duty and is supplied with an auxiliary switch contact that automatically removes control power following a breaker tri...

Страница 13: ...p thus preventing potential nuisance tripping due to momentary loss of volt age The time delay unit is 11 Accessories for Drawout Breakers cont mounted externally to the breaker It is rated 125Vdc 250...

Страница 14: ...l DL1616B which may be pur chased commercially Long time pickup The long time pickup indicator moves through two transitions As the current in any phase reaches 95 of its setpoint the LTPU LED begins...

Страница 15: ...uator trip signal from the microprocessor to the trip actuator The trip actuator is a low energy positive action tripping device The low level trip signal counteracts the strength of the actuator s pe...

Страница 16: ...reaker will withstand for short peri ods of time to allow downstream devices to clear faults without tripping the breaker Settings are adjustable in increments of the breaker current setting C See Tab...

Страница 17: ...es not exceed 1200 amps There are three ground fault delay bands of 1 MIN 2 INT 3 MAX ranging from 100 ms to 350 ms The I2 t function adds an I2 t slope to the square corner of the ground fault time c...

Страница 18: ...trips initiated by the trip unit will cause the bell alarm if so equipped to operate Reset of the bell alarm contacts and the mechanical lockout if provided is by way of the reset button on the breake...

Страница 19: ...life lithium batteries provide program ming and display power to the trip unit s LCD on com mand With the breaker disconnected from the source and load the trip unit can be removed from the breaker an...

Страница 20: ...change state whenever the trip actuator causes the breaker to open The bell alarm is not activated by any other manual or electrical tripping means Standard And Optional Protective Functions Standard...

Страница 21: ...s current setting or value of LT Long time delay Instantaneous Function Standard All WavePro breakers are available with standard adjustable instantaneous trip function The instantaneous trip point es...

Страница 22: ...ings such that the maximum setting does not exceed 1200 amps There are three ground fault delay bands of 1 MIN 2 INT 3 MAX ranging from 100 ms to 350 ms The I2 t function modifies the square corner of...

Страница 23: ...2 0 3 0 5 0 7 0 20 25 30 35 WPX 08 1 5 2 0 3 0 5 0 9 0 10 0 13 0 15 0 40 45 50 60 WPF 08 7 0 9 0 10 0 WPS 16 WPH 16 MVT Plus PM MVT Plus PM WPF 16 1 5 thru 15 0 in steps of 0 20 thru 0 60 in steps of...

Страница 24: ...ckup protection If a fault occurs between two breakers equipped with zone selective interlocking the upstream breaker would clear the fault on the minimum delay band because it receives no interlock s...

Страница 25: ...yed without the use of the trip unit internal batteries similar to the operation of the MicroVersaTrip PM trip unit Communications Output The communications network uses a pair of shielded twisted wir...

Страница 26: ...ve relaying functions are selected any combi nation of the following protective relays can be enabled All relay functions combine both an adjustable setpoint and an adjustable discrete not inverse tim...

Страница 27: ...rs use the same programming keypads All functions ordered are selectable and displayed Programming display and keypad Function Selects the mode of the display Setup Metering or Status Select Chooses t...

Страница 28: ...ombinations for MicroVersaTrip Plus PM Breaker Frame Rating Sensor Rating Available Rating Plugs Amps CT In 800 150 60 80 100 125 150 800 400 150 200 225 250 300 400 800 1600 800 300 400 450 500 600 7...

Страница 29: ...1200 TR20C1200GF TR20C1200GFD TR20B1200 1500 N A N A N A TR20B1500 1600 TR20C1600 TR20C1600GF TR20C1600GFD TR20B1600 2000 TR20C2000 TR20C2000GF TR20C2000GFD TR20B2000 1200 TR32C1200 TR32C1200GF TR32C1...

Страница 30: ...lass L fuse J 7 1600A Class L fuse K 8 2000A Class L fuse L 9 2500A Silver L fuse M 800A Welder limiter N 1600A Welder limiter Q 2000A Welder limiter R 1000A Welder limiter Z Frame Sensor Code See Not...

Страница 31: ...DC P 125v DC Q 250v DC R 240v 60Hz T 240v 50Hz W Requires min 4 stage auxiliary switch and shunt trip Shunt Trip 1 Code none X 120VAC 60Hz 1 208VAC 60Hz 2 240VAC 60Hz 3 70VAC 60Hz 4 120VAC 50Hz 5 208V...

Страница 32: ...25WATT FOR 240VAC WAVEPRO CIRCUIT BREAKER ELEC MAN OPERATED OPTIONAL SECOND SHUNTTRIP DEVICE MOMENTARY TC 2 Y MB FUSE X FUSE 2 C14 1 TRIP AUX 13 13C L C5 Z W1 W2 SHOT ONE S OS 2 1 V RES NOTE 10 Y Y TC...

Страница 33: ...S 20 WPS 32 WPS 40 WPS 50 FRAMES ONLY A28 A29 31 47 T ZSI IN A30 A31 30 46 T ZSI OUT MVT PLUS PM PM READY ONL Y INTERLOCKING INPUT OUTPUT ZONE SELECTIVE TRIP UNIT A24 A25 T NS 49 50 INPUT NEUTRAL SENS...

Страница 34: ...ied to accept lower rated fuses WPF 16 breakers equipped with 2000A and lower fuses cannot be upgraded to 2500A fuses The maximum trip rating for a WPF 16 breaker is 1200A when furnished with other th...

Страница 35: ...ower circuit breakers at altitudes greater than 6 600 feet their continuous current rating must be modified because a higher temperature use will be experi enced for a given current rating The voltage...

Страница 36: ...34 Time Current Curves...

Страница 37: ...Time Current Curves cont 35...

Страница 38: ...36 Time Current Curves cont...

Страница 39: ...and breaking rated current at rated maximum voltage and 2 additional no load mechanical on off operations per Table 36 1 Table 36 1 Endurance requirements for low voltage AC power circuit breakers Sh...

Страница 40: ...hat it is immune to nuisance trips or improper operation when nearby walkie talkies are used 6 Wiggins Immunity Tests are performed to ensure the breaker will not nuisance trip when exposed to a high...

Страница 41: ...condary disconnect points All breaker control circuits as well as inputs and outputs for the trip unit shall be wired through the sec ondary disconnects Secondary disconnect points shall be self align...

Страница 42: ...able I2 t ramp f SELECT ONE OF THE FOLLOWING IF GROUND FAULT PROTECTION IS REQUIRED 1 Adjustable ground fault pickup and time delay with three delay bands and switchable I2 t ramp 2 Defeatable ground...

Страница 43: ...lay with three delay bands and switchable I2 t ramp and or adjustable instanta neous pickup f SELECT ONE OF THE FOLLOWING IF GROUND FAULT PROTECTION IS REQUIRED 1 Adjustable ground fault pickup and ti...

Страница 44: ...imagination at work GE Consumer Industrial 41 Woodford Avenue Plainville CT 06062 www GEindustrial com 2004 General Electric Company DET 167C 0904 BL...

Отзывы: