Trip Characteristics — MicroVersaTrip Plus™ and PM™ 

Defeatable Ground-Fault Protection (Optional) — 

Not UL Listed

A defeatable ground-fault function is offered for users who
want the ability to enable or disable ground-fault protection
depending on special circumstances. When this type of
ground-fault protection is ordered, in addition to the nor-
mal ground-fault settings, the user can disable ground-fault
protection during programming by setting the delay to OFF.

Switchable Short Time or Instantaneous OR Switchable Short
Time or Instantaneous and Ground-Fault Protection (Optional) –
Switchable Ground Fault Not UL Listed

Special breaker applications may require the ability to selec-
tively enable and disable the short circuit protection and/or
ground fault protection of the breaker. Switchable short
time or instantaneous allows either the short time function
or the instantaneous function to be disabled for use in
unique situations such as a breaker functioning as a spare
for several feeders with different trip characteristics. Both
short time and instantaneous functions can be enabled but
both cannot be disabled. Switchable ground fault protection
is similar to the defeatable ground fault function in that it
can be enabled or disabled via the ground fault delay setting.

Zone Selective Interlocking (Optional)

Traditional means of obtaining selectivity between main and
feeder breakers is to set the furthest downstream device with
the lowest time delays, and increase time delays of upstream
devices. The disadvantage of this is that upstream portions
of the system must endure high values of fault current until
time-out occurs.

Breakers equipped with MicroVersaTrip Plus™ or
MicroVersaTrip PM™ trip units can provide improved 
protection to zones between breakers through the use of
Zone Selective Interlocking. When a downstream breaker
(feeder) detects a fault, it signals the upstream device
(main) to shift to its preset time delay band, allowing the
downstream device to clear the fault while the upstream
device provides backup protection. If a fault occurs between
two breakers equipped with zone selective interlocking, the
upstream breaker would clear the fault on the minimum
delay band because it receives no interlock signal from a
downstream breaker, thus minimizing the duration that 
the fault would exist before being cleared.

Zone selective interlocking is available for either ground
fault only or both ground-fault and short-time functions.
The zone selective interlocking feature requires a zone
selective interlock module (ZSIM) for each zone. The 
module is an intermediate control device used between
upstream and downstream circuit breaker to communicate
with the short-time and ground-fault zone selective interlock

functions of the MicroVersaTrip Plus and MicroVersaTrip
PM trip units. The module (Cat. No. TIM1) requires
120/208/240 Vac control power, 15 VA maximum. 
The module can communicate with up to 30 downstream 
breakers and up to 6 upstream breakers provided all 
breakers share the same zone.

Multi-zone selective interlocking

Operation Of MicroVersaTrip PM Trip Units

MicroVersaTrip PM trip units add communications 
capability with remote host computers and the GE POWER
LEADER™ Power Management System. In addition, the 
user can choose to add metering with or without additional 
protective relaying. In the block diagram (page 23) of the
MicroVersaTrip PM trip unit, note that there are two addi-
tional sets of inputs — voltage inputs from each phase and 
a 24 Vdc input from an external power supply. Additionally,
there is a communications input/output link to the POWER
LEADER system.

Voltage Inputs

Voltage Inputs to the MicroVersaTrip PM trip unit are
required for both metering and protective relays. Voltage
inputs require three delta or wye-connected potential 
transformers with 120 Vac secondaries, and an external 
voltage module that further conditions the voltage signals
for use by the trip units microprocessor. A single set of
external voltage modules can serve the requirements of 
up to 16 trip units.

Bus

Zone 0      CB1

Zone 1      CB2

Zone 2      CB3

Zone 3      CB4

Motor

Source

L1

L2

ZSIM No.1

ZSIM No.2

M

V
T

M

V
T

M

V
T

M

V
T

M

V
T

“Output” from Trip unit

“Input” to Trip unit

ZSIM No.1

Downstream 
Connections

Upstr eam 
Connections

Wiring

ZSIM No.3

Содержание WavePro LVPCB

Страница 1: ...WaveProTM Low Voltage Power Circuit Breakers Application Guide The Ultimate Assurance In Uptime And Reliability Now with 100kAIC ratings...

Страница 2: ...Plus and PM 17 Trip Units MicroVersaTrip Plus 18 Trip Characteristics MicroVersaTrip Plus and PM 19 Trip Characteristics Power MicroVersaTrip Plus and PM 21 Trip Units MicroVersaTrip PM 23 MicroVersaT...

Страница 3: ...rings Operation of the breaker can be accomplished through manual OPEN CLOSE buttons on the escutcheon The escutcheon also includes indicators for closing spring status main contact status and breaker...

Страница 4: ...remote close accessory CLOSE and TRIP push button covers sealable remote charge indicator switch 8 Sealable door over the trip unit trip settings can be viewed but not changed 9 Easy access to key bre...

Страница 5: ...S 50 5000 85 85 85 WPX 50 5000 100 100 100 WPS 08 800 30 42 30 WPH 08 800 42 50 42 WPX 08 800 65 65 65 240 WPS 16 1600 50 65 50 WPH 16 1600 65 65 65 254 WPS 20 2000 65 65 65 WPS 32 3200 65 85 65 WPH 3...

Страница 6: ...ures 5 Padlocking devices A Supplied on all breakers the padlocking device allows up to three padlocks 1 4 to 3 8 diameter shank to be installed to keep the breaker mechanically trip free B A drawout...

Страница 7: ...5 Features Characteristics cont 2 1A 9 3 1B 7 5A 12 6 11 10 8 9 4 5C...

Страница 8: ...ing the ability to block automatic recharging of the springs if required by the breaker application The anti pump feature in the closing circuit provides one closing operation of the breaker for each...

Страница 9: ...s that may have automatic control For Power and MicroVersaTrip Plus trip units the bell alarm will operate for overload short circuit and ground fault trips For MicroVersaTrip PM trip units the bell a...

Страница 10: ...lling and removing the WavePro draw out breakers It attaches to the breaker to provide stability when lifting the breaker from its drawout rails Pickup points on the breaker and lifting tool are WP 08...

Страница 11: ...Table 9 1 Field installable Remote Charge Indicator Switch kit catalog numbers Remote Close Accessory with One Shot Electronic Close Circuit Field installable kit available The remote close accessory...

Страница 12: ...not require the use of a shunt trip The shunt trip coil is rated for intermittent duty and is supplied with an auxiliary switch contact that automatically removes control power following a breaker tri...

Страница 13: ...p thus preventing potential nuisance tripping due to momentary loss of volt age The time delay unit is 11 Accessories for Drawout Breakers cont mounted externally to the breaker It is rated 125Vdc 250...

Страница 14: ...l DL1616B which may be pur chased commercially Long time pickup The long time pickup indicator moves through two transitions As the current in any phase reaches 95 of its setpoint the LTPU LED begins...

Страница 15: ...uator trip signal from the microprocessor to the trip actuator The trip actuator is a low energy positive action tripping device The low level trip signal counteracts the strength of the actuator s pe...

Страница 16: ...reaker will withstand for short peri ods of time to allow downstream devices to clear faults without tripping the breaker Settings are adjustable in increments of the breaker current setting C See Tab...

Страница 17: ...es not exceed 1200 amps There are three ground fault delay bands of 1 MIN 2 INT 3 MAX ranging from 100 ms to 350 ms The I2 t function adds an I2 t slope to the square corner of the ground fault time c...

Страница 18: ...trips initiated by the trip unit will cause the bell alarm if so equipped to operate Reset of the bell alarm contacts and the mechanical lockout if provided is by way of the reset button on the breake...

Страница 19: ...life lithium batteries provide program ming and display power to the trip unit s LCD on com mand With the breaker disconnected from the source and load the trip unit can be removed from the breaker an...

Страница 20: ...change state whenever the trip actuator causes the breaker to open The bell alarm is not activated by any other manual or electrical tripping means Standard And Optional Protective Functions Standard...

Страница 21: ...s current setting or value of LT Long time delay Instantaneous Function Standard All WavePro breakers are available with standard adjustable instantaneous trip function The instantaneous trip point es...

Страница 22: ...ings such that the maximum setting does not exceed 1200 amps There are three ground fault delay bands of 1 MIN 2 INT 3 MAX ranging from 100 ms to 350 ms The I2 t function modifies the square corner of...

Страница 23: ...2 0 3 0 5 0 7 0 20 25 30 35 WPX 08 1 5 2 0 3 0 5 0 9 0 10 0 13 0 15 0 40 45 50 60 WPF 08 7 0 9 0 10 0 WPS 16 WPH 16 MVT Plus PM MVT Plus PM WPF 16 1 5 thru 15 0 in steps of 0 20 thru 0 60 in steps of...

Страница 24: ...ckup protection If a fault occurs between two breakers equipped with zone selective interlocking the upstream breaker would clear the fault on the minimum delay band because it receives no interlock s...

Страница 25: ...yed without the use of the trip unit internal batteries similar to the operation of the MicroVersaTrip PM trip unit Communications Output The communications network uses a pair of shielded twisted wir...

Страница 26: ...ve relaying functions are selected any combi nation of the following protective relays can be enabled All relay functions combine both an adjustable setpoint and an adjustable discrete not inverse tim...

Страница 27: ...rs use the same programming keypads All functions ordered are selectable and displayed Programming display and keypad Function Selects the mode of the display Setup Metering or Status Select Chooses t...

Страница 28: ...ombinations for MicroVersaTrip Plus PM Breaker Frame Rating Sensor Rating Available Rating Plugs Amps CT In 800 150 60 80 100 125 150 800 400 150 200 225 250 300 400 800 1600 800 300 400 450 500 600 7...

Страница 29: ...1200 TR20C1200GF TR20C1200GFD TR20B1200 1500 N A N A N A TR20B1500 1600 TR20C1600 TR20C1600GF TR20C1600GFD TR20B1600 2000 TR20C2000 TR20C2000GF TR20C2000GFD TR20B2000 1200 TR32C1200 TR32C1200GF TR32C1...

Страница 30: ...lass L fuse J 7 1600A Class L fuse K 8 2000A Class L fuse L 9 2500A Silver L fuse M 800A Welder limiter N 1600A Welder limiter Q 2000A Welder limiter R 1000A Welder limiter Z Frame Sensor Code See Not...

Страница 31: ...DC P 125v DC Q 250v DC R 240v 60Hz T 240v 50Hz W Requires min 4 stage auxiliary switch and shunt trip Shunt Trip 1 Code none X 120VAC 60Hz 1 208VAC 60Hz 2 240VAC 60Hz 3 70VAC 60Hz 4 120VAC 50Hz 5 208V...

Страница 32: ...25WATT FOR 240VAC WAVEPRO CIRCUIT BREAKER ELEC MAN OPERATED OPTIONAL SECOND SHUNTTRIP DEVICE MOMENTARY TC 2 Y MB FUSE X FUSE 2 C14 1 TRIP AUX 13 13C L C5 Z W1 W2 SHOT ONE S OS 2 1 V RES NOTE 10 Y Y TC...

Страница 33: ...S 20 WPS 32 WPS 40 WPS 50 FRAMES ONLY A28 A29 31 47 T ZSI IN A30 A31 30 46 T ZSI OUT MVT PLUS PM PM READY ONL Y INTERLOCKING INPUT OUTPUT ZONE SELECTIVE TRIP UNIT A24 A25 T NS 49 50 INPUT NEUTRAL SENS...

Страница 34: ...ied to accept lower rated fuses WPF 16 breakers equipped with 2000A and lower fuses cannot be upgraded to 2500A fuses The maximum trip rating for a WPF 16 breaker is 1200A when furnished with other th...

Страница 35: ...ower circuit breakers at altitudes greater than 6 600 feet their continuous current rating must be modified because a higher temperature use will be experi enced for a given current rating The voltage...

Страница 36: ...34 Time Current Curves...

Страница 37: ...Time Current Curves cont 35...

Страница 38: ...36 Time Current Curves cont...

Страница 39: ...and breaking rated current at rated maximum voltage and 2 additional no load mechanical on off operations per Table 36 1 Table 36 1 Endurance requirements for low voltage AC power circuit breakers Sh...

Страница 40: ...hat it is immune to nuisance trips or improper operation when nearby walkie talkies are used 6 Wiggins Immunity Tests are performed to ensure the breaker will not nuisance trip when exposed to a high...

Страница 41: ...condary disconnect points All breaker control circuits as well as inputs and outputs for the trip unit shall be wired through the sec ondary disconnects Secondary disconnect points shall be self align...

Страница 42: ...able I2 t ramp f SELECT ONE OF THE FOLLOWING IF GROUND FAULT PROTECTION IS REQUIRED 1 Adjustable ground fault pickup and time delay with three delay bands and switchable I2 t ramp 2 Defeatable ground...

Страница 43: ...lay with three delay bands and switchable I2 t ramp and or adjustable instanta neous pickup f SELECT ONE OF THE FOLLOWING IF GROUND FAULT PROTECTION IS REQUIRED 1 Adjustable ground fault pickup and ti...

Страница 44: ...imagination at work GE Consumer Industrial 41 Woodford Avenue Plainville CT 06062 www GEindustrial com 2004 General Electric Company DET 167C 0904 BL...

Отзывы: