background image

1

WavePro

TM

Low Voltage Power Circuit Breakers

WavePro circuit breakers are the newest generation of GE
low voltage power circuit breakers. WavePro builds on the
experience of the AKR breaker line to bring new conve-
nience and safety features while retaining the robustness of
GE’s long-standing power circuit breaker products. WavePro
breakers are ANSI designed and carry the UL label. They
are designed to withstand short circuit stresses equal to their
short time interrupting ratings. This means that maximum
selectivity with downstream devices can be attained because
instantaneous trips are not required to achieve the breaker’s
short circuit rating. This attests to the ruggedness of the
WavePro design and places it ahead of insulated case 
breakers and other maker’s power circuit breakers in many
critical applications. WavePro breakers can be applied on
power systems from 208 to 600 volts and have current ratings
of 800 through 5000 amperes. Short circuit interrupting
ratings for WavePro breakers range from 30kA to 200kA
rms symmetrical.

Why Specify Low Voltage Power Circuit Breakers?

All circuit breakers perform the function of basic circuit
protection. What separates low voltage power circuit break-
ers (LVPCB) from insulated case (ICCB) and molded case
(MCCB) circuit breakers are features and ratings that make
the equipment application safer to operate, easier to main-
tain, and maximize equipment uptime. Some of the key dif-
ferences are:

LVPCB

ICCB/MCCB

Maximum ambient 

40°C equipment ambient

25°C equipment ambient

operating temperature

(55°C breaker ambient)

(40°C breaker ambient)

Nominal/Maximum 240/

254v

240/240v

operating voltage

480/

508v

480/480v

600/

635v

600/600v

Short circuit testing

30 cycles

@ 15% PF

3 cycles @ 20% PF

(Instantaneous trips 

not required

for interrupting rating)

Switchgear/Switchboard 

Drawout (closed door)

Drawout (not closed door)

mounting

or Stationary

Greater Convenience And Operational Safety

General Electric pioneered the closed door drawout design
for low voltage power circuit breakers with the AK line of
breakers. WavePro retains that safety feature and adds more
features. Control, status and circuit information are all 
available on the front of the breaker with the breaker 
compartment door closed. All breakers have a flush-mounted
handle for charging the closing springs. Operation of the
breaker can be accomplished through manual OPEN/
CLOSE buttons on the escutcheon. The escutcheon also
includes indicators for closing spring status, main contact 
status, and breaker drawout position. Trip units are mounted
behind a sealable cover for easy viewing of the display and
access to the rating plug test receptacle. When equipped 
with a bell alarm, the target/reset button is also mounted in
the escutcheon. The charging handle and the close and open
push buttons are double insulated from live components to
provide additional operator safety. A standard padlock device
allows you to install up to three padlocks to prevent acciden-
tal or unauthorized closing of the breaker.

Field Installable Accessories

WavePro breakers feature standardized wiring to dedicated
secondary disconnect points for all accessories. This allows
you to easily add accessories to the breaker should it
become necessary after the breaker is installed. Field 
installable accessories include auxiliary switch, shunt trip,
undervoltage device, electrical lockout device, bell alarm
with or without lockout, “hidden-on” button, close and trip
push button covers, remote close accessory, remote charge
indicator and operations counter. Trip units can be upgraded
easily and the breakers can be made “power management
ready” so that stepping up to the top-of-the-line MicroVersaTrip
PM trip unit is as easy as replacing the trip unit — no 
additional modifications to the breaker are required.

Three Choices Of Advanced, Solid-State Trip Units

For basic functionality, the Power+™ trip unit gives you
straightforward means of providing overload and short 
circuit protection on a WavePro circuit breaker. Tripping
characteristics are easily adjusted by simple-to-use rotary
switches. The trip unit is upgradeable to ground fault by 
simply inserting a ground fault rating plug. An optional 
target module allows for target monitoring and also functions
as a trip unit health indicator. Enhanced MicroVersaTrip
Plus™ and MicroVersaTrip PM™ trip units give you two ways
to monitor and control the WavePro breaker with unprece-
dented ease. A simple keypad lets you program and display a
variety of functions including tripping characteristics, remote
communications, status information and protective relaying,
and allows integration with GE POWER LEADER™ Power
Management Systems. The trip unit display also allows view-
ing of many standard metering parameters as well as pickup
alarms, trip target indications and fault status information.

Содержание WavePro LVPCB

Страница 1: ...WaveProTM Low Voltage Power Circuit Breakers Application Guide The Ultimate Assurance In Uptime And Reliability Now with 100kAIC ratings...

Страница 2: ...Plus and PM 17 Trip Units MicroVersaTrip Plus 18 Trip Characteristics MicroVersaTrip Plus and PM 19 Trip Characteristics Power MicroVersaTrip Plus and PM 21 Trip Units MicroVersaTrip PM 23 MicroVersaT...

Страница 3: ...rings Operation of the breaker can be accomplished through manual OPEN CLOSE buttons on the escutcheon The escutcheon also includes indicators for closing spring status main contact status and breaker...

Страница 4: ...remote close accessory CLOSE and TRIP push button covers sealable remote charge indicator switch 8 Sealable door over the trip unit trip settings can be viewed but not changed 9 Easy access to key bre...

Страница 5: ...S 50 5000 85 85 85 WPX 50 5000 100 100 100 WPS 08 800 30 42 30 WPH 08 800 42 50 42 WPX 08 800 65 65 65 240 WPS 16 1600 50 65 50 WPH 16 1600 65 65 65 254 WPS 20 2000 65 65 65 WPS 32 3200 65 85 65 WPH 3...

Страница 6: ...ures 5 Padlocking devices A Supplied on all breakers the padlocking device allows up to three padlocks 1 4 to 3 8 diameter shank to be installed to keep the breaker mechanically trip free B A drawout...

Страница 7: ...5 Features Characteristics cont 2 1A 9 3 1B 7 5A 12 6 11 10 8 9 4 5C...

Страница 8: ...ing the ability to block automatic recharging of the springs if required by the breaker application The anti pump feature in the closing circuit provides one closing operation of the breaker for each...

Страница 9: ...s that may have automatic control For Power and MicroVersaTrip Plus trip units the bell alarm will operate for overload short circuit and ground fault trips For MicroVersaTrip PM trip units the bell a...

Страница 10: ...lling and removing the WavePro draw out breakers It attaches to the breaker to provide stability when lifting the breaker from its drawout rails Pickup points on the breaker and lifting tool are WP 08...

Страница 11: ...Table 9 1 Field installable Remote Charge Indicator Switch kit catalog numbers Remote Close Accessory with One Shot Electronic Close Circuit Field installable kit available The remote close accessory...

Страница 12: ...not require the use of a shunt trip The shunt trip coil is rated for intermittent duty and is supplied with an auxiliary switch contact that automatically removes control power following a breaker tri...

Страница 13: ...p thus preventing potential nuisance tripping due to momentary loss of volt age The time delay unit is 11 Accessories for Drawout Breakers cont mounted externally to the breaker It is rated 125Vdc 250...

Страница 14: ...l DL1616B which may be pur chased commercially Long time pickup The long time pickup indicator moves through two transitions As the current in any phase reaches 95 of its setpoint the LTPU LED begins...

Страница 15: ...uator trip signal from the microprocessor to the trip actuator The trip actuator is a low energy positive action tripping device The low level trip signal counteracts the strength of the actuator s pe...

Страница 16: ...reaker will withstand for short peri ods of time to allow downstream devices to clear faults without tripping the breaker Settings are adjustable in increments of the breaker current setting C See Tab...

Страница 17: ...es not exceed 1200 amps There are three ground fault delay bands of 1 MIN 2 INT 3 MAX ranging from 100 ms to 350 ms The I2 t function adds an I2 t slope to the square corner of the ground fault time c...

Страница 18: ...trips initiated by the trip unit will cause the bell alarm if so equipped to operate Reset of the bell alarm contacts and the mechanical lockout if provided is by way of the reset button on the breake...

Страница 19: ...life lithium batteries provide program ming and display power to the trip unit s LCD on com mand With the breaker disconnected from the source and load the trip unit can be removed from the breaker an...

Страница 20: ...change state whenever the trip actuator causes the breaker to open The bell alarm is not activated by any other manual or electrical tripping means Standard And Optional Protective Functions Standard...

Страница 21: ...s current setting or value of LT Long time delay Instantaneous Function Standard All WavePro breakers are available with standard adjustable instantaneous trip function The instantaneous trip point es...

Страница 22: ...ings such that the maximum setting does not exceed 1200 amps There are three ground fault delay bands of 1 MIN 2 INT 3 MAX ranging from 100 ms to 350 ms The I2 t function modifies the square corner of...

Страница 23: ...2 0 3 0 5 0 7 0 20 25 30 35 WPX 08 1 5 2 0 3 0 5 0 9 0 10 0 13 0 15 0 40 45 50 60 WPF 08 7 0 9 0 10 0 WPS 16 WPH 16 MVT Plus PM MVT Plus PM WPF 16 1 5 thru 15 0 in steps of 0 20 thru 0 60 in steps of...

Страница 24: ...ckup protection If a fault occurs between two breakers equipped with zone selective interlocking the upstream breaker would clear the fault on the minimum delay band because it receives no interlock s...

Страница 25: ...yed without the use of the trip unit internal batteries similar to the operation of the MicroVersaTrip PM trip unit Communications Output The communications network uses a pair of shielded twisted wir...

Страница 26: ...ve relaying functions are selected any combi nation of the following protective relays can be enabled All relay functions combine both an adjustable setpoint and an adjustable discrete not inverse tim...

Страница 27: ...rs use the same programming keypads All functions ordered are selectable and displayed Programming display and keypad Function Selects the mode of the display Setup Metering or Status Select Chooses t...

Страница 28: ...ombinations for MicroVersaTrip Plus PM Breaker Frame Rating Sensor Rating Available Rating Plugs Amps CT In 800 150 60 80 100 125 150 800 400 150 200 225 250 300 400 800 1600 800 300 400 450 500 600 7...

Страница 29: ...1200 TR20C1200GF TR20C1200GFD TR20B1200 1500 N A N A N A TR20B1500 1600 TR20C1600 TR20C1600GF TR20C1600GFD TR20B1600 2000 TR20C2000 TR20C2000GF TR20C2000GFD TR20B2000 1200 TR32C1200 TR32C1200GF TR32C1...

Страница 30: ...lass L fuse J 7 1600A Class L fuse K 8 2000A Class L fuse L 9 2500A Silver L fuse M 800A Welder limiter N 1600A Welder limiter Q 2000A Welder limiter R 1000A Welder limiter Z Frame Sensor Code See Not...

Страница 31: ...DC P 125v DC Q 250v DC R 240v 60Hz T 240v 50Hz W Requires min 4 stage auxiliary switch and shunt trip Shunt Trip 1 Code none X 120VAC 60Hz 1 208VAC 60Hz 2 240VAC 60Hz 3 70VAC 60Hz 4 120VAC 50Hz 5 208V...

Страница 32: ...25WATT FOR 240VAC WAVEPRO CIRCUIT BREAKER ELEC MAN OPERATED OPTIONAL SECOND SHUNTTRIP DEVICE MOMENTARY TC 2 Y MB FUSE X FUSE 2 C14 1 TRIP AUX 13 13C L C5 Z W1 W2 SHOT ONE S OS 2 1 V RES NOTE 10 Y Y TC...

Страница 33: ...S 20 WPS 32 WPS 40 WPS 50 FRAMES ONLY A28 A29 31 47 T ZSI IN A30 A31 30 46 T ZSI OUT MVT PLUS PM PM READY ONL Y INTERLOCKING INPUT OUTPUT ZONE SELECTIVE TRIP UNIT A24 A25 T NS 49 50 INPUT NEUTRAL SENS...

Страница 34: ...ied to accept lower rated fuses WPF 16 breakers equipped with 2000A and lower fuses cannot be upgraded to 2500A fuses The maximum trip rating for a WPF 16 breaker is 1200A when furnished with other th...

Страница 35: ...ower circuit breakers at altitudes greater than 6 600 feet their continuous current rating must be modified because a higher temperature use will be experi enced for a given current rating The voltage...

Страница 36: ...34 Time Current Curves...

Страница 37: ...Time Current Curves cont 35...

Страница 38: ...36 Time Current Curves cont...

Страница 39: ...and breaking rated current at rated maximum voltage and 2 additional no load mechanical on off operations per Table 36 1 Table 36 1 Endurance requirements for low voltage AC power circuit breakers Sh...

Страница 40: ...hat it is immune to nuisance trips or improper operation when nearby walkie talkies are used 6 Wiggins Immunity Tests are performed to ensure the breaker will not nuisance trip when exposed to a high...

Страница 41: ...condary disconnect points All breaker control circuits as well as inputs and outputs for the trip unit shall be wired through the sec ondary disconnects Secondary disconnect points shall be self align...

Страница 42: ...able I2 t ramp f SELECT ONE OF THE FOLLOWING IF GROUND FAULT PROTECTION IS REQUIRED 1 Adjustable ground fault pickup and time delay with three delay bands and switchable I2 t ramp 2 Defeatable ground...

Страница 43: ...lay with three delay bands and switchable I2 t ramp and or adjustable instanta neous pickup f SELECT ONE OF THE FOLLOWING IF GROUND FAULT PROTECTION IS REQUIRED 1 Adjustable ground fault pickup and ti...

Страница 44: ...imagination at work GE Consumer Industrial 41 Woodford Avenue Plainville CT 06062 www GEindustrial com 2004 General Electric Company DET 167C 0904 BL...

Отзывы: