GFK-1911B
Chapter 6 Diagnostics
6-3
6
Possible LED combinations
No.
UM
US
BF
FS
FN
Error
Remedy
1
)
Voltage supply U
M
and U
S
absent
Check voltage supply U
M
and
U
S
2)
Voltage supply U
M
absent
Check voltage supply U
M
3)
Voltage supply U
S
absent
Check voltage supply U
S
4)
No error, everything OK
5)
No communication on
Profibus
Correct Profibus address
on the NIU
Correct Profibus master
settings
Remove Profibus cable
fault
6)
Number of pulses on FN
indicates the type of error
See the table that follows.
7)
Number of pulses on FN
indicates the error number
See the table that follows.
8)
Outputting failsafe values
(IC670PBI002 only)
Switch master to Run state,
check communication with
master.
Set “data exchange mode”
parameter on the NIU to “data
exchange without operate”
Key: