Permissible Operating Temperature Range
With an increased ambient temperature, you must calculate the permissible
operating temperature range for the calculated power loss.
Set P
tot
= P
HOU
.
P
tot
= 2.4W - [(T
U
+ 5°C) / 37.5K/W]
After changing the formula, the maximum permissible ambient temperature
is calculated with this load as:
T
U
= (2.4W - P
tot
) x 37.5K/W - 5°C
P
tot
= 1.38W (from the calculated power loss of the electronics)
T
U
= (2.4W - 1.38W) x 37.5K/W - 5°C
T
U
= 1.02W x 37.5K/W - 5°C
T
U
= 33.25°C
With full load on both outputs, you can operate this module up to an ambient
temperature of 33°C (91.4°F). If you never operate the outputs
simultaneously and if a set output consumes a current of 2A you can
operate the module up to:
P
tot
= 0.18W + 1 x [0.20W + (2A)
2
x 0.1
Ω
)]
P
tot
= 0.18W + 0.60W
P
tot
= 0.78W
T
U
= (2.4W - P
tot
) x 37.5K/W - 5°C
P
tot
= 0.78 W (from the calculated power loss of the electronics)
T
U
= (2.4W - 0.78W) x 37.5K/W - 5°C
T
U
= 1.62W x 37.5K/W - 5°C
T
U
= 55.75°C
T
U
= 55°C (maximum permissible ambient temperature)
As the maximum permissible ambient temperature is 55°C (131°F) you can
work in the entire permissible temperature range under the above
mentioned conditions. This leads to a simultaneity of 50% at 55°C indicated
in the data sheet.
Содержание VersaPoint IC220PBI002
Страница 4: ......
Страница 10: ...Contents x VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B...
Страница 80: ...5 14 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 5...
Страница 100: ...6 20 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 6...
Страница 166: ...A 10 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B A...