GFK-1911B
Chapter 7 Configuration
7-19
7
Specifying the Active Configuration
1
. Specify the address on the station using DIP switches
1
to 7 and select
the operating mode using DIP switch 8 = ON.
Connect the modules that represent the subgroup of the maximum
configuration. In the hardware configurator, configure only the "PD-PCP
x words" module (recommendation: x > = 8).
The address can be freely defined in the PLC memory within the
framework of the options provided by the PLC. The module has no
specific requirements.
2. Specify the active configuration.
In the example, the modules in slots 3, 4, and 6 should be deactivated.
According to the description of index 6, the value is 2C 00 00 00 00 00
00 00.
Write request (master -> slave)
Data (8 Words VC1)
Data Structure
04 00 00 06 00 08
2C 00 00
00 00 00 00 00 I 00 00
Write/Slot/Index high/Index
low/Subind
ex/Length/Data I 2 bytes unused
Write response (slave -> master)
Data (8 Words VC1)
Data Structure
84 00 I 00 00 00 0
0 00 00 00
00 00 00 00 00 00 00
Write re
sponse/Status I
1
4 bytes unused
Clear request (master -> slave)
Data (8 Words VC1)
Data Structure
00 xx xx xx xx xx xx xx xx xx
xx xx xx xx xx xx
Clear
Clear response (slave -> master)
Data (8 Words VC1)
Data Structure
00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00
Clear response
Содержание VersaPoint IC220PBI002
Страница 4: ......
Страница 10: ...Contents x VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B...
Страница 80: ...5 14 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 5...
Страница 100: ...6 20 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 6...
Страница 166: ...A 10 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B A...