GFK-1911B
Appendix A Reference Data
A-9
A
Test Voltages
Test Voltages
Isolating distance
Test voltage
Technology for 24V range (up to 60VDC)
5 V supply incoming network cable /
5 V supply outgoing network cable
500VAC, 50Hz,
1
min.
5 V supply incoming network cable /
7.5 V communications power, 24V NIU supply
500VAC, 50Hz,
1
min.
5 V supply incoming network cable /
24V main supply, 24V segment supply
500VAC, 50Hz,
1
min.
5 V supply incoming network cable /
Functional earth ground
500VAC, 50Hz,
1
min.
5 V supply outgoing network cable /
7.5 V communications power, 24V NIU supply
500VAC, 50Hz,
1
min.
5 V supply outgoing network cable /
24V main supply, 24V segment supply
500VAC, 50Hz,
1
min.
5 V supply outgoing network cable /
Functional earth ground
500VAC, 50Hz,
1
min.
7.5 V communications power, 24V NIU supply Functional /
earth ground
500VAC, 50Hz,
1
min.
7.5 V communications power, 24V NIU supply /
24V main supply, 24V segment supply
500VAC, 50Hz,
1
min.
24V main supply, 24V segment supply
Functional earth ground
500VAC, 50Hz,
1
min.
Technology for range up to 250VDC
Bus logic / I/O devices
2500VAC, 50Hz,
1
min.
Technology for 230VAC range single-phase (up to 253VAC)
Bus logic / I/O devices
2500VAC, 50Hz,
1
min.
Relay outputs
Main contact / N/O contact
1
000VAC, 50Hz,
1
min.
Relay contact / bus logic
2500VAC, 50Hz,
1
min.
Содержание VersaPoint IC220PBI002
Страница 4: ......
Страница 10: ...Contents x VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B...
Страница 80: ...5 14 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 5...
Страница 100: ...6 20 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 6...
Страница 166: ...A 10 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B A...