GFK-1911B
Chapter 8 Communications
8-19
8
Continue Fragment
Byte 1
Service
Byte 2
Data block, if required
...
Byte n
Data block, if required
Byte 1 - Service in continue fragment
7
6 5 4 3 2 1 0
Request/
response
0
1
Fragment number (01
hex
- 1F
hex
)
Bit 7
Request/response
0 = Request
1 = Response
Bits 6 to 5
Fragment type
01 = Continue fragment
Bits 4 to 0
Counter
01
hex
to 0F
hex
Fragment number. If more fragments are required,
continue with 0 after 1Fhex.
End Fragment
Byte 1
Service
Byte 2
Data block, if required
...
Byte n
Data block, if required
Byte 1 - Service in end fragment
7
6 5 4 3 2 1 0
Request/
response
1 0
Reserved
Bit 7
Request/response
0 = Request
1 = Response
Bits 6 to 5
Fragment type
10 = Last fragment (end fragment)
Bits 4 to 0
Reserved