manualshive.com logo in svg
background image

UR Family Firmware 5.81 - Release Notes 

Firmware 5.81 

Line Differential Systems L90, L60, L30 

N  The Line Current Differential Systems to support hybrid conventional–HardFiber line terminal wiring 

Products: L30, L90 
Corrected firmware: 5.81 
Description: This FW version enables the L90 Line Current Differential System to support hybrid wiring 

configurations where one line terminal uses traditional wiring, and the other line terminal uses the 

HardFiber technology. This applies for two and three-line terminal schemes. Previous firmware versions 

supported either traditional or HardFiber wiring when both line terminals had the same kind of wiring 

(both traditional or both HardFiber). 
GE tracking number: 581-1 

Common Protection Elements 

Ground Time Overcurrent elements have been changed to use the correct signal input when set to 

“phasor” 

Products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, T35, T60 
Corrected firmware: 5.81 
Description: The “input setting” within the overcurrent elements determines the type of signal input the 

elements use for operation. Phasors or RMS current can be set to the “input setting.” Changes to the 

Ground Time Overcurrent elements ensure that they operate based on the ground current phasor 

magnitude when their “input setting” is “phasor.” Previous firmware versions have the Ground Time 

Overcurrent elements operating based on the “RMS” current value whether “RMS” or “phasor” were set to 

the “input setting”. 
GE tracking number: 581-2 

The Synchrocheck elements have been changed to correctly detect a dead source when set to “DV1 

XOR DV2” 

Products: C60, D30, D60, F60, G30, G60, L30, L60, L90, N60, T60 
Corrected firmware: 5.81 
Description: When the “Dead Source Select” setting within the Synchrocheck element is set to “DV1 XOR 

DV2,” the element has to determine two conditions: a) one of the sources is dead evaluating existing 

voltage vs. the “Dead V1/2 Max Volts” setting, and b) the other source is live evaluating existing voltage vs. 

the “Live V1/2 Min Volts” setting. Previous firmware versions have the Synchrocheck elements verifying 

dead source by evaluating the existing voltage vs. the “Live V1/2 Min Volts” setting when set as mentioned 

above.  And then the element incorrectly declares dead source. Changes to the Synchrocheck elements 

ensure that they evaluate the existing voltage vs. the right setting. This issue does not affect customers 

who have the “Dead Source Select” setting set different to “DV1 XOR DV2”. 
GE tracking number: 581-3 

The Autoreclose element has been changed to ensure it goes to “lockout” state when the element is 

blocked and unblocked while in “reclose in progress” 

Products: D30, F35, F60, L30 
Corrected firmware: 5.81 
Description: If the operand set to the “AR Block” setting is activated when a reclose cycle is in progress, the 

autoreclose element goes to “Lockout” state. If the “AR Block” is subsequently removed, previous firmware 

Содержание UR series

Страница 1: ...84 20 October 2021 In the following descriptions a category letter is placed to the left of the title See the table at the end of this document for descriptions of the categories Major firmware releas...

Страница 2: ...B30 has been enhanced to have individual phase instantaneous overcurrent elements per current source Products B30 Corrected firmware 5 80 Description Four additional phase instantaneous overcurrent el...

Страница 3: ...the thermal status it can be used in a permissive scheme to allow re energizing a capacitor bank after tripping on an overload condition GE tracking number 580 7 Feeder Protection Systems F35 F60 N E...

Страница 4: ...erminal line differential scheme raises PFLL Fail synchronization status and CH fail operands at all three terminals when both communication channels fail on at least one terminal However if only one...

Страница 5: ...compared with the negative sequence component This also increases the element security GE tracking number 580 14 Communications N Line Differential Systems L30 and L90 to support the IEC61850 logical...

Страница 6: ...values and other PMU settings have not been affected See the N60 instruction manual for details GE tracking number 580 19 M Changes to the PMU data recording function ensure an accurate time stamping...

Страница 7: ...ate a Brick Trouble condition Products B30 C30 C60 C70 D30 D60 F35 F60 G30 G60 L30 L90 M60 N60 T35 T60 Corrected firmware 5 80 Description Brick Trouble is a self reset minor self test warning message...

Страница 8: ...ent elements operating based on the RMS current value whether RMS or phasor were set to the input setting GE tracking number 581 2 P The Synchrocheck elements have been changed to correctly detect a d...

Страница 9: ...w the elements output to momentarily change state when the relay power cycles Customers using the non Volatile Latches for protection or control purposes are advised to upgrade their relay firmware ve...

Страница 10: ...al element that are displayed by the relay might not meet the design accuracy of 5 when restraint current values are below 0 11xIn These changes do not affect the operation of the ground line differen...

Страница 11: ...t communication channels can be applied After recovering from a channel failure L90 devices must synchronize for the Line Differential Element to go back to normal operation The synchronization proces...

Страница 12: ...Stall current at 100 volts to give motors a longer acceleration time This is especially useful when protecting very high inertia motors Negative sequence currents are now filtered to properly bias th...

Страница 13: ...waveform metered signal are checked to validate a good signal GE tracking number 720 57 U The Negative Sequence and Neutral Directional Overcurrent elements have been modified to deliver enhanced sec...

Страница 14: ...et Priority and VLAN addresses in an Ethernet data frame The existing implementation allows users to set a single value of priority that applies to all GOOSE messages That singular value of priority i...

Страница 15: ...s was modified to comply with the IEC61850 standard 00 intermediate 11 Bad For further information see the UR device instruction manual GE tracking number 590 12 C UR IEC6870 5 104 implementation has...

Страница 16: ...n calculate net difference or monitor UR actual analog values Previous firmware versions can allow FlexElements to improperly apply the unit base value when IEC61850 GOOSE analog are set as the FlexEl...

Страница 17: ...port a data filter that discards any data for the debug port The debug port traffic is only allowed when a factory service password requirement is met End users having UR devices with an Ethernet port...

Страница 18: ...ch forces a discrepancy between the internal event recorder and communication protocol time stamp A UR relay generating dozens of events within one protection pass period can also lead protection and...

Страница 19: ...Without channel monitoring commissioning or troubleshooting procedures with loopback tests can become complex This firmware version changes the UR devices loopback mode to allow channel monitoring whi...

Страница 20: ...Family Firmware 5 83 Release Notes boot up This firmware release ensures that the firmware in the Brick is maintained when connecting a Brick to URs with earlier firmware versions GE tracking number 6...

Страница 21: ...ng number 603 1 P Improved accuracy of bus differential pickup in the region between Low and High breakpoints Products B30 B90 Impacted firmware All to 6 06 7 00 to 7 28 7 30 to 7 82 Corrected firmwar...

Страница 22: ...g testing if needed using the Test Mode Function GE tracking number 728 10 F Improved security in differential elements Products B30 B90 G30 G60 M60 T35 T60 Impacted firmware All to 6 06 7 00 to 7 27...

Страница 23: ...xample enabling the source incorrectly triggers Module Failure 07 GE tracking number 605 11 E Improved Restricted Ground Fault RGF element Products All with Restricted Ground Fault element F60 G30 G60...

Страница 24: ...6 02 and 6 04 and above Corrected firmware 5 84 6 03 Workaround None Description Setting group switching is a fast operation that under normal conditions should not trigger any self test alarm Some UR...

Страница 25: ...ppens due to last valid status values being substituted with default values if even one sample is detected as bad in the frame With the new release at least two bad frames are required two protection...

Страница 26: ...corrected versions ensure that the firmware upgrade process is completed with the first reboot no second reboot is required GE tracking number 721 1 Platform U The Equipment Mismatch self test warnin...

Страница 27: ...CNT DIFF PKP and XFMR PCNT DIFF 5TH operands for Transformer Percent Differential element Products G30 T35 T60 Impacted firmware All to 6 05 7 00 to 7 26 7 30 to 7 61 Corrected firmware 5 84 6 06 7 27...

Страница 28: ...mers with limited communication experience to set their GOOSE messages GE Tracking Number 580 24 N New Backup Restore modes for UR Setup software environment file Applicable UR Setup UR Engineer Descr...

Страница 29: ...tons One the language and front panel are changed by the user the software tool updates the order code which erases all the settings Settings must be previously saved and uploaded to the relay after t...

Страница 30: ...omers having UR devices with FW version 5 7x or 5 8x should use VP UR Engineer 5 80 GE Tracking Number 580 28 G Software exceptions Applicable UR Engineer Description The following software exceptions...

Страница 31: ...being inadvertently removed when the relay order code had software option 12 or 13 and the process bus HardFiber module C70 Phase Unbalance Operands not appearing correctly in FlexLogic graphical view...

Страница 32: ...ns Changes to or problems with text messages LEDs and user pushbuttons R Changed incomplete or false relay records Changes to or problems with relay records oscillography demand fault reports and so o...

Страница 33: ...olutions 650 Markland Street Markham Ontario Canada L6C 0M1 Worldwide telephone 1 905 927 7070 Europe Middle East Africa telephone 34 94 485 88 54 North America toll free 1 800 547 8629 Fax 1 905 927...

Отзывы: