Installation Instructions
11
11
BATHROOM OR BEDROOM INSTALLATION
• The appliance
MUST
be vented to the outdoors. See
EXHAUST INFORMATION
section 3 & 4.
• The installation must conform with local codes or, in the
absence of local codes, with the
NATIONAL ELECTRICAL
CODE, ANSI/NFPA NO. 70.
9
MOBILE OR MANUFACTURED HOME
INSTALLATION
• Installation
MUST
conform to the
MANUFACTURED
HOME CONSTRUCTION & SAFETY STANDARD,
TITLE 24, PART 32-80
or, when such standard is not
applicable, with
AMERICAN NATIONAL STANDARD FOR
MOBILE HOME, ANSI/NFPA NO. 501B.
• The appliance
MUST
be vented to the outdoors with
the termination securely fastened to the mobile home
structure.
• The vent
MUST NOT
be terminated beneath a mobile or
manufactured home.
• The vent duct material
MUST BE METAL
.
• Do not use sheet metal screws or other fastening
devices which extend into the interior of the exhaust
vent.
• See section 2 for electrical connection information.
10
ALCOVE OR CLOSET INSTALLATION
• If your appliance is approved for installation in an
alcove or closet, it will be stated on a label on the
appliance back.
• TO PREVENT LARGE AMOUNTS OF LINT AND MOISTURE
FROM ACCUMULATING AND TO MAINTAIN DRYING
EFFICIENCY, THIS MACHINE MUST BE EXHAUSTED
OUTDOORS.
• Do not install this appliance with less than the minimum
clearances shown above.
CONSIDERATION MUST BE GIVEN TO PROVIDE
ADEQUATE CLEARANCES FOR INSTALLATION
AND SERVICE.
CAUTION:
DO NOT INSTALL THIS
APPLIANCE IN A CLOSET WITH A SOLID DOOR.
1”
0”
0”
0”
1”
DOOR VENTILATION OPENING (27”
MODELS)
A minimum of 120 square inches of opening, equally
divided at top and bottom, is required. Air openings are
required to be unobstructed when a door is installed.
A louvered door with equivalent air openings for the
full length of the door is acceptable.
When louvers or registers are placed in door openings, the
free air openings of the louvers or registers must equal 120
square inches.
DOOR VENTILATION OPENING (24”
MODELS)
A minimum of 72 square inches of opening is required. Air
openings are required to be unobstructed when a door is
installed. A louvered door with equivalent air openings for
the full length of the door is acceptable.
When louvers or registers are placed in door openings, the
free air openings of the louvers or registers must equal 72
square inches.
60 Sq. In.
60 Sq. In.
27” Model
48 Sq. In.
24 Sq. In.
24” Model