102
—
The indoor fan motor is burned or breaks or has
the heat protector malfunction.
Replace the fan motor or the defective part.
The built in heat protector in the motor is tripped
off frequently due to overheat as the result of
abnormal motor operation.
Replace the fan motor
Wrong connection
Make the correct connection based on the circuit
drawing.
The fan does not
run when it is set to
supply air.
The fan capacitor has open circuit or is damaged.
Replace the fan capacitor with the same model and
specification
The outdoor fan motor is damaged.
Replace the fan motor
Wrong connection
Make the correct connection based on the circuit
drawing.
When unit is cooling
or heating, the
compressor runs
but outdoor fan
doesn't run
The outdoor fan capacitor is damaged.
Replace the fan capacitor
Compressor malfunction
Replace the compressor
Breakage of running capacitor of compressor
Replace the capacitor
The voltage is too low or too high.
Manostat is recommended.
Wrong connection
Make the correct connection based on the circuit
drawing.
When cooling or
heating, outdoor fan
runs, compressor
doesn't run.
Malfunction of the protector
Check with a multimeter and see if the contacts
conduct when the compressor is not overheated. If
not, replace the protector.
Too much coolant
Adjust the volume of the refrigerant
The capillary is blocked and the sucking
temperature is increased.
Replace capillary
The compressor does not run normally,
jammed or blocked. The air discharge valve is
damaged.
Replace the compressor
Protection is
activated due to an
overheat
compressor.
Malfunction of the protector
Replace the protector
Inadequate torque of swing motor
Wrong connection
Swing blade does
not rotate.
The controller is damaged(IC2003 is damaged,
the swing relay can not a close
)
Firstly check if the wire connection is correct; if not,
replace relevant element at malfunction point.
Содержание PRO AIR 107
Страница 2: ... 1 Summary and features Model Remark PRO AIR 107 IN PRO AIR 107 OUT 1Ph 230V 50Hz R410A 1 ...
Страница 4: ... 3 Model Remark PRO AIR 218 IN PRO AIR 218 OUT 1Ph 230V 50Hz R410A ...
Страница 5: ... 4 Model Remark GE AIR 326 IN1 GE AIR 326 IN2 GE AIR 326 OUT 1Ph 230V 50Hz R407C ...
Страница 6: ... 5 Model Remark GE AIR 428 IN GE AIR 428 OUT 1Ph 230V 50Hz R407C ...
Страница 20: ... 19 4 2 Outline and installation dimensions of indoor unit 20 Handle 60cm Bolt Nut Spanner ...
Страница 21: ... 20 4 3 Outline and installation dimensions of indoor units 25 32 Handle Unit mm 500 Bolt Nut Spanner ...
Страница 71: ... 70 Explosive view and parts list Explosive view of parts and components of indoor unit 9 ...
Страница 75: ... 74 Explosive view of parts and components of outdoor unit ...
Страница 77: ... 76 Explosive view of parts and components of outdoor unit frequency converter ...
Страница 79: ... 78 Explosive view of parts of outdoor unit one driving two ...
Страница 81: ... 80 Explosive view of parts of outdoor unit one driving three ...
Страница 83: ... 82 Explosive view of parts of outdoor unit one driving four ...
Страница 101: ... 100 ...