Installation Instructions
DuCtWorK CAlCulAtIonS
Calculate total Equivalent Ductwork length
Equivalent
Number
Equivalent
Duct Pieces
Length* x
Used =
Length
6” round
straight
1 ft .
x
( )
†
=
ft .
3
1
⁄
4
” x 10"
straight
1 ft .
x
( )
†
=
ft .
6”, 90°
elbow
15 ft . x
( ) =
ft .
6”, 45°
elbow
9 ft .
x
( )
=
ft .
24” max .
flexible
metal offset
adapter
34 ft . x
( )
=
ft .
3
1
⁄
4
” x 10”
90° elbow
16 ft . x
( ) =
ft .
3
1
⁄
4
” x 10”
45° elbow
5 ft .
x
( )
=
ft .
3
1
⁄
4
” x 10”
90° flat elbow 18 ft . x
( )
=
ft .
6” round
to 3
1
⁄
4
” x 10”
transition
7 ft .
x
( ) =
ft .
Subtotal Column 1 =
ft .
* Equivalent lengths of duct pieces are based on actual
tests and reflect requirements for good venting
performance with any downdraft cooktop .
† Measure and list feet of straight duct used . Count and
list the quantity of all other duct pieces for the “Number
Used” of each type .
ImPortAnt:
For maximum efficiency, use the shortest and straightest
duct run possible, with as few fittings as possible .
For satisfactory performance, the duct run should not
exceed 100 feet equivalent length.
Venting performance is improved by using larger
diameter duct .
Equivalent
Number
Equivalent
Duct Pieces
Length* x
Used =
Length
6” round
to 3
1
⁄
4
” x 10”
transition
90° elbow
20 ft .
x
( ) =
ft .
3
1
⁄
4
” x 10”
to 6” round
transition
5 ft .
x
( ) =
ft .
3
1
⁄
4
” x 10”
to 6” round
transition
90° elbow
12 ft . x
( )
=
ft .
6” round
wall cap
with damper 21 ft .
x
( ) =
ft .
3
1
⁄
4
” x 10”
wall cap
with damper 27 ft .
x
( ) =
ft .
6” round
roof cap
20 ft . x
( ) =
ft .
6” round
roof vent
24 ft .
x
( ) =
ft .
Subtotal Column 2 =
ft .
Subtotal Column 1 =
ft .
totAl Du CtWorK =
ft .
Should not exceed 100 fee
t .
Do not use flexible plastic ducting.
Vent installation should not exceed 100 feet
equivalent length .