GEK-113000T
F650 Digital Bay Controller
C-11
APPENDIX C
C.1 FACTORY DEFAULT SETTINGS
C
SETPOINT > PROTECTION ELEMENTS > SENSITIVE GROUND CURRENT > SENSITIVE GROUND IOC
SENSITIVE GROUND IOC 1> SENSITIVE GROUND IOC 2 > SENSITIVE GROUND IOC 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Input type
Input
PHASOR(DFT)
N/A
[PHASOR – RMS]
Pickup level
Pickup Level
0.100
0.001 A
[0.005 : 16.000]
Trip time
Trip Delay
0.00
0.01 s
[0.00 : 900.00]
Reset time
Reset Delay
0.00
0.01 s
[0.00 : 900.00]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > SENSITIVE GROUND CURRENT > ISOLATED GROUND IOC
ISOLATED GROUND IOC 1> ISOLATED GROUND IOC 2 > ISOLATED GROUND IOC 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
High Voltage level
Vh Level
20
1 V
[2 : 70]
Low Current level
Il LEVEL
0.005
0.001 A
[0.005 : 0.400]
Low Voltage level
Vl LEVEL
2
1 V
[2 : 70]
High Current level
Ih LEVEL
0.025
0.001 A
[0.005 : 0.400]
Operation time
Delay
0.00
0.01 s
[0.00 : 900.00]
Deviation time to instantaneous
Time to inst
0.00
0.01 s
[0.00 : 900.00]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > SENSITIVE GROUND CURRENT > SENSITIVE GROUND DIRECTIONAL >
SENSITIVE GROUND DIRECTIONAL 1> SENSITIVE GROUND DIRECTIONAL 2 > SENSITIVE GROUND DIRECTIONAL 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Maximum Torque Angle
MTA
-45
1 Deg
[-90 : +90]
Operation Direction
Direction
FORWARD
N/A
[FORWARD – REVERSE]
Block logic type
Block Logic
PERMISSION
N/A
[BLOCK – PERMISSION]
Polarization voltage threshold
Pol V Threshold
10
1 V
[0 : 300]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > NEGATIVE SEQUENCE CURRENT > NEGATIVE SEQUENCE TOC >
NEGATIVE SEQUENCE TOC 1> NEGATIVE SEQUENCE TOC 2 > NEGATIVE SEQUENCE TOC 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup level
Pickup Level
1.00
0.01 A
[0.05 : 160.00]
Curve shape
Curve
IEEE Ext Inv
N/A
[See list of curves]
Time Dial
TD Multiplier
1.00
0.01 s
[0.00 : 900.00]
Reset type
Reset
INSTANTANEOUS
N/A
[INSTANTANEOUS –
LINEAR]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin GEK-113000T
Страница 5: ...4 F650 Digital Bay Controller GEK 113000T TABLE OF CONTENTS ...
Страница 25: ...1 20 F650 Digital Bay Controller GEK 113000T 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 127: ...3 70 F650 Digital Bay Controller GEK 113000T 3 3 WEB SERVER 3 HUMAN INTERFACES SETTINGS ACTUAL VALUES 3 ...
Страница 169: ...6 26 F650 Digital Bay Controller GEK 113000T 6 17 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6 ...
Страница 175: ...7 6 F650 Digital Bay Controller GEK 113000T 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7 ...
Страница 215: ...A 36 F650 Digital Bay Controller GEK 113000T A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 259: ...D 2 F650 Digital Bay Controller GEK 113000T D 1 GE MULTILIN WARRANTY APPENDIXD D ...