C-18
F650 Digital Bay Controller
GEK-113000T
C.1 FACTORY DEFAULT SETTINGS
APPENDIX C
C
SETPOINT > CONTROL ELEMENTS >POWER
WATT GND FLT HIGH 1> WATT GND FLT HIGH 2 > WATT GND FLT HIGH 3
WATT GND FLT LOW 1> WATT GND FLT LOW 2 > WATT GND FLT LOW 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED-ENABLED]
Supervision minimum voltage
Voltage Pickup Level
2
0.01 V
[2.00 : 70.00]
Source of operating current.
Current selection
IN
N/A
[IN-IG]
Pickup Level for Overcurrent
OC Pickup Level
0,005
0.001A
[0.005 : 0.400]
Pickup Delay for Overcurrent
OC Pickup Delay
0,2
0.01 s
[0.00 : 600.00]
Pickup Level for operating Power
Power Pickup
0,01
0.01 W
[0.01 : 4.50]
Max torque angle
MTA
0
1 Deg
[0 : 360]
Pickup Delay for Operating Power
Power Pickup Delay
0,2
0.01 s
[0.00 : 600.00]
Curve shape
Curve
DEFINITE TIME
N/A
[DEFINITE TIME -
INVERSE TIME - USER
CURVE A - USER CURVE
B - USER CURVE C -
USER CURVE D]
Multiplier
Multiplier
1
0.01 s
[0.02 : 2.00]
Snapshot event generation
Snapshot Event
DISABLED
N/A
[DISABLED-ENABLED]
Содержание Multilin GEK-113000T
Страница 5: ...4 F650 Digital Bay Controller GEK 113000T TABLE OF CONTENTS ...
Страница 25: ...1 20 F650 Digital Bay Controller GEK 113000T 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 127: ...3 70 F650 Digital Bay Controller GEK 113000T 3 3 WEB SERVER 3 HUMAN INTERFACES SETTINGS ACTUAL VALUES 3 ...
Страница 169: ...6 26 F650 Digital Bay Controller GEK 113000T 6 17 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6 ...
Страница 175: ...7 6 F650 Digital Bay Controller GEK 113000T 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7 ...
Страница 215: ...A 36 F650 Digital Bay Controller GEK 113000T A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 259: ...D 2 F650 Digital Bay Controller GEK 113000T D 1 GE MULTILIN WARRANTY APPENDIXD D ...