GEK-113000T
F650 Digital Bay Controller
C-17
APPENDIX C
C.1 FACTORY DEFAULT SETTINGS
C
SETPOINT > CONTROL ELEMENTS > PULSE COUNTERS
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Pulse counter enabling setting
CntPulses Enabled X
DISABLED
N/A
[DISABLED – ENABLED]
Name of the pulse counter
CntPulses Name X
Pulse Counter 1
N/A
N/A
Multiplier factor for the pulse counter
CntPulses Factor X
1.000
0.001
[0.000 : 65000.000]
Overflow value for the pulse counter
CntPulses Overflow X 65535
1
[0 : 1000000]
Board selection for the pulse counter
CntPulses Board
Origin X
F
N/A
[F,G,H,I]
Input index inside the selected board
CntPulses Input Origin
X
1
1
[1 : 32]
Note: X is the pulse counter index, up to 8.
SETPOINT > CONTROL ELEMENTS > ANALOG COMPARATORS
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Generic Analog Function Permission
Analog Function
DISABLED
N/A
[DISABLED – ENABLED]
Generic Snapshot Events Generation
Analog Snapshot
Events
DISABLED
N/A
[DISABLED – ENABLED]
Analog Input Value Selection
Analog Input X
None
N/A
[All available analog values]
Analog Maximum Threshold Value
Analog Maximum X
1.000
0.001
[-100000.000 : 100000.000]
Analog Minimum Threshold Value
Analog Minimum X
1.000
0.001
[-100000.000 : 100000.000]
Analog Delay for Activation Signal
Analog Delay X
0.00
0.01 s
[0.00 : 900.00]
Analog Hysteresis for the Deadband
Analog Hysteresis X
1.0
0.1
[0.0 : 50.0]
Analog Direction for Activation Inside
or Outside the Deadband
Analog Direction X
OUT
N/A
[IN-OUT]
Note: X is the analog comparator index, up to 20
SETPOINT > CONTROL ELEMENTS > FREQUENCY RATE OF CHANGE
FREQUENCY RATE OF CHANGE 1 > FREQUENCY RATE OF CHANGE 2 > FREQUENCY RATE OF CHANGE 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Direction of the frequency change
Freq. Rate Trend
INCREASING
N/A
[INCREASING -
DECREASING - BI-
DIRECTIONAL]
Operation Value in Hz/s
Freq. Rate Pickup
0.50
0.01 Hz/s
[0.10 : 10.00]
Minimum required voltage in %
nominal voltage
Freq. Rate OV Supv
40.00
0.01%
[0.00 : 110.00]
Minimum Frequency Threshold
Freq. Rate Min
45.00
0.01 Hz
[20.00 : 80.00]
Maximum Frequency Threshold
Freq. Rate Max
65.00
0.01 Hz
[20.00 : 80.00]
Frequency rate Trip Delay
Freq. Rate Delay
0.00
0.01 s
[0.00 : 60.00]
Snapshot Events Generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > LOAD ENCROACHMENT
LOAD ENCROACHMENT 1 > LOAD ENCROACHMENT 2 > LOAD ENCROACHMENT 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Minimum positive-sequence voltage
required
Min. Voltage
25.00
0.01 V
[0.00 : 300.00]
Impedance reach of the element
Reach
1.00
0.01 Ohm
[0.02 : 250.00]
Angle (Size of the blocking region)
Angle
5
1 Deg
[5 : 50]
Trip Time
Pickup Delay
0.000
0.001 s
[0.000 : 65.535]
Reset Time
Reset Delay
0.000
0.001 s
[0.000 : 65.535]
Snapshot Events Generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin GEK-113000T
Страница 5: ...4 F650 Digital Bay Controller GEK 113000T TABLE OF CONTENTS ...
Страница 25: ...1 20 F650 Digital Bay Controller GEK 113000T 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 127: ...3 70 F650 Digital Bay Controller GEK 113000T 3 3 WEB SERVER 3 HUMAN INTERFACES SETTINGS ACTUAL VALUES 3 ...
Страница 169: ...6 26 F650 Digital Bay Controller GEK 113000T 6 17 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6 ...
Страница 175: ...7 6 F650 Digital Bay Controller GEK 113000T 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7 ...
Страница 215: ...A 36 F650 Digital Bay Controller GEK 113000T A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 259: ...D 2 F650 Digital Bay Controller GEK 113000T D 1 GE MULTILIN WARRANTY APPENDIXD D ...