ECO-mode
The
LanPro
®
-U
UPS is equipped with the ‘ECO-mode’ feature. If the feature is enabled, the load is operated on
utility through the electronic bypass switch. If the utility is interrupted or out of limits the load is automatically
transferred to the inverter. Operating the load on utility improves the efficiency of the UPS with 5-8% and saves on
energy costs. We advise not to use the ECO-mode in case of an unstable utility.
After enabling the ECO-mode (please refer to service screens 5.3.3) the
standard menu
changes to:
NOTE:
If
LanPro
®
-U
units operate in parallel, the ECO-mode feature is not available.
5.5.6
Auto restart
If this feature is enabled and the unit has shut down (e.g. due to overload) the UPS will start up automatically when
the normal situation is restored. The off-factory setting is: enabled.
If the auto restart feature is disabled the unit will not automatically restart when the normal situation is restored but
the display will show:
After ‘Enter’ the unit will restart. See also 5.3.3 ‘service screens’.
5.5.7
Superior Battery Management
-
Load dependent battery-end voltage:
The allowable final battery voltage depends on the discharge current:
the higher the current, the lower the 'end-of-discharge' battery voltage. This gives maximum capacity without
over discharging. Over discharging results in failure to recover normal capacity and in shortened battery life.
-
Equalize mode:
When switched on for the first time the UPS will start boost-charging the batteries for 15
hours in order to equalize all battery voltages.
-
Boost mode:
If after a discharge the battery voltage is lower than 240Vdc, the UPS will charge the batteries
with a boost charge voltage of 285Vdc. This enables fast recharging of the batteries. The programmed
battery charging mode will change from boost charge into float charge after boost charging twice.
-
Temperature compensated battery charging:
This feature reduces the battery charge voltage with
increasing temperature (-18mV/
°
C or -32.4mV/
°
F per 12V battery). As a result poor charging of the batteries
under low temperature conditions and overcharging of the batteries under high temperature conditions are
prevented.