LX: OPM_LPA_11U_5K0_10K_1US_V021
21
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
GE Digital Energy
g
5.1 Description of Front and Rear Panel
1
LCD screen
2x16 characters, shows UPS system data, status messages, settings.
The language is selectable: English, German, French, Italian,
Spanish. Section 5.3.4 describes the selection procedure.
2-4
Push-buttons
With the button keypads ‘down’ (2) and ‘up’ (4) you can scroll through
the several screens, with keypad 'reset/enter' (3) a selection is
confirmed. Keypad activity is accompanied by a short beep. If there is
no keypad activity during 20 seconds the LCD screen will return to the
default screen (except for the service screens, see section 5.3.3).
5
LED 'operation' indicates normal operation.
6
LED ‘alarm’, indicates an alarm situation, accompanied by alarm
message(s) on the display and a sounding buzzer.
See section 5.3.2 for more information.
7
Switch ‘UPS on/off’, turns on/off the complete UPS, including the
automatic bypass!
8
Circuit breaker ‘Utility on/off’, protection fuse for utility input and
battery charger.
9
Circuit breaker ‘Bypass on/off’, fuse to protect the system in case of
severe overload or short circuit in the UPS load.
10
Manual Bypass Switch:
1 = Load on UPS
2 = Load on utility
WARNING:
In position 2, if the input line is energized, the
output is also live regardless the position of the circuit
breakers ‘utility’ and ‘bypass’.
11
Cover plate, behind it:
11a
Output terminals
11b
Input terminals
12
RS232/Contact Interface Card, with:
12a
- RS232 Interface Port (see section 6.1)
- Emergency shutdown (see 4.4.1 and 6.2)
- Battery disconnected, pin 1-2 (can be used for external
signaling).
13
Free option slot for plug-in cards:
- Relay Card (see 6.3)
- SNMP Card (see 6.4)
14
Option slot for RPA (Redundant Parallel Architecture) Card. Not
available yet.
15
DC socket / connector.
16
Battery fuse holder
17
Conduit box
18
Cable inlet
Figure 19 :
Front and rear panel
6
5
1
2
4
3
16
7 8 9
10
11a
11b
17
15
14
18
13
12
12a
11