Bushing data alarm
Description
Secondary Phase C – C1% Polar
Plot Level Status
The C1% polar plot amplitude is above a given
threshold on an area defined by Secondary C (see
C1% Polar plot level warning and C1% Polar plot
level alarm in Table 5)
Primary Phase A – C1% Level
Status
The Primary A measured input current has
changed beyond a given threshold (see C1% level
warning and C1% level alarm in Table 5)
Primary Phase B – C1% Level
Status
The Primary B measured input current has
changed beyond a given threshold (see C1% level
warning and C1% level alarm in Table 5)
Primary Phase C – C1% Level
Status
The Primary B measured input current has
changed beyond a given threshold (see C1% level
warning and C1% level alarm in Table 5)
Secondary Phase A – C1% Level
Status
The Secondary A measured input current has
changed beyond a given threshold (see C1% level
warning and C1% level alarm in Table 5)
Secondary Phase B – C1% Level
Status
The Secondary B measured input current has
changed beyond a given threshold (see C1% level
warning and C1% level alarm in Table 5)
Secondary Phase C – C1% Level
Status
The Secondary B measured input current has
changed beyond a given threshold (see C1% level
warning and C1% level alarm in Table 5)
Primary Phase A – PF% Polar
Plot Level Status
The PF% polar plot amplitude is above a given
threshold on an area defined by Primary A (see
PF% Polar plot level warning and PF% Polar plot
level alarm in Table 5)
Primary Phase B – PF % Polar
Plot Level Status
The PF% polar plot amplitude is above a given
threshold on an area defined by Primary B (see
PF% Polar plot level warning and PF% Polar plot
level alarm in Table 5)
Primary Phase C – PF % Polar
Plot Level Status
The PF% polar plot amplitude is above a given
threshold on an area defined by Primary C (see
PF% Polar plot level warning and PF% Polar plot
level alarm in Table 5)