Intellix
™
BMT 330 User Manual
Page 36
BMT330UM
v1.0
20-Jun-16
Parameter
Suggested Value for both Primary & Secondary
3
Default
Allowable range
4
C1% Polar plot level warning
5%
0 to 100 %
C1% Polar plot level alarm
10%
0 to 100 %
C1% level warning
15%
0 to 100 %
C1% level alarm
20%
0 to 100 %
Table 5: Bushing Insulation Alarm Settings
After entering settings for Primary bushings, repeat procedure and enter settings
for Secondary bushings if applicable.
Write the alarm settings to the Intellix™ BMT 330 by pressing the
“
Write/Program
” button. It is advisable to save the configuration file by pressing the
“
Save Settings To File
” button.