Intellix
™
BMT 330 User Manual
Page 48
BMT330UM
v1.0
20-Jun-16
The PF% measurements are calculated based on the bushing phase angle
measurements and the expected phase angles presented in the Bushing
Settings tab.
The PD Max displayed on this page is the maximum PD value for the cycle.
The log file PD Max is the maximum value of the PD averaged over each
cycle. This PD Max is refreshed every 2 seconds.
PD (pC) is the amplitude (apparent charge) of the PD event.
PD count is the number of partial discharge events per cycle
PDI (mW) is the average power associated to a PD event (as defined in IEC
60270).
Sensors
Figure 19: Sensors tab.