Page 21
Intellix
™
BMT 330 User Manual
BMT330UM
v1.0
20-Jun-16
Default Serial Settings for
Port 1
(RS-485/USB)
Slave Address
3
Baud Rate
9600
Parity Check
Even
Transmission Mode
RTU
Default Serial Settings for
Port 0
(optional
Ethernet/Fibre Optic)
Slave Address
3
Baud Rate
38400
Parity Check
Even
Transmission Mode
RTU
Table 1: Communication serial default settings
If a serial connection is selected the flow control on the PC side must be off.
Please refer to the serial hardware documentation. For a modem this may be done
either via AT commands (see below) of the modem driver’s interface.
To validate the “
Communication
” settings, click the “
Ping
” button.
Once the settings are confirmed, it is suggested that they are saved for
future reference, by pressing the “
Save Setting to File
” button. A Windows
File Dialogue will open, to allow you to name the settings file (in
configuration, cfg, format) and set the save location, as shown in Figure 7
below.
Note
: Most pages/ tabs have a “
Save Setting to File
” button. In each case,
it will save just the configuration settings from that page/tab only. The
option to save
all
configuration settings in one file requires the “Service”
Function to obtain access to the
Utilities > Program Settings
tab; refer to
the companion Intellix™ BMT 330 Service Manual.