5-4
PACSystems* RX3i
PROFINET Controller Manual
– December 2011
GFK-2571A
5
Transitioning to Firmware Update Mode
The module transitions to firmware update mode for any of the following reasons:
1. Winloader has commanded the module to enter firmware update mode. This is normal when a
firmware update has been initiated from Winloader.
2. The PNC does not have a valid firmware image at power-up. The PNC performs checks to
determine the firmware image is valid and has not been corrupted before it begins execution. If
the validation fails, firmware update mode is activated until a valid image has been stored.
For more information about firmware update mode and using Winloader, please see chapter 2,
Installation.