GFK-2571A
Chapter 3 Configuration
3-17
3
Adding VersaMax PROFINET Scanner Power Supplies
The VersaMax PNS has connectors for either one or two power supplies. If necessary, additional
power supplies can also be located between modules in the remote node.
To configure the one or two power supplies that will be installed directly on the PNS module, right-
click on the Slot 0 icon in the Navigator, then select Change Submodule List. A list of VersaMax
power supplies appears.
In the Submodule list for slot 0, expand the list of power supplies and select the correct power supply
from the list. Drag it to the slot on the left. Slot 0, subslot 2 is the left power supply slot. Slot 0,
subslot 3 is the right power supply slot. (To delete a module after moving it, select the module on the
left and press the keyboard Delete key).
Click OK to add the selected module(s) to the configuration. The Navigator shows the added power
supply or power supplies under slot 0.
Adding power supplies to the configuration sets up power supply alarms. Alarms will be triggered if
the power supply is configured but not working, or configured in the wrong subslot. These power
supplies have no configurable parameters, but their power supply and GSDML details can be viewed
by double-clicking on a power supply or right-clicking and selecting Configure.