5-20
PACSystems* RX3i
PROFINET Controller Manual
– December 2011
GFK-2571A
5
Group/
Category/
Type/
Description
Description
Cause
Recommended
Correction
9-6-11-0
Multiple Media
Redundancy
Managers are no
longer present on the
network.
The PNC is configured as a
Media Redundancy Manager
and it had detected that multiple
Media Redundancy Managers
were on the network, but now
those other managers are no
longer present.
No action necessary. The network is
expected to only have a single Media
Redundancy Manager present.
9-6-12-0
The Media
Redundancy
Manager has
detected that the
network ring has
been broken.
The PROFINET MRP network
ring is broken.
The MRP Ethernet ring is broken.
Possible causes include damaged or
disconnected cable or power loss to a
node or switch. Locate and repair the
cause(s).
9-6-13-0
The Media
Redundancy
Manager has
detected that the
network ring has
been repaired.
The PROFINET MRP network
ring is closed/okay.
No action necessary. This is the normal,
expected state of an MRP Ethernet ring.
9-11-3-1
Invalid MAC address
detected.
PNC no longer has a valid MAC
address.
Contact customer service.
9-11-3-3
Media redundancy
configuration error.
The PNC has encountered a
problem attempting to configure
media redundancy operation.
Contact customer service.
9-11-5-x
Internal runtime error.
PNC has encountered an
internal error during its
operation.
Contact customer service.
9-18-1-1
PNC exceeded its
recommended
operating
temperature.
The temperature detected by the
PNC has exceeded its safe
operating temperature.
Reduce the temperature of the
environment where the PNC is operating.
9-18-1-2
Watchdog Timeout
Error
PNC application code restarted
due to a hardware watchdog
timeout.
Contact customer service.
9-69-0-0
PNC has become
heavily loaded.
The PNC has become heavily
loaded with activity (Continued
use in this mode may cause
degradation of system
performance (possibly including
delayed IO updates) and
potential loss of network
communications.
Reduce load on PNC. One or more of
the following can be tried to reduce load:
Increase the configured update rate
value (i.e. IO received less
frequently) of one or more
PROFINET Devices configured on
the PNC.
Reduce the number of PROFINET
Devices configured on the PNC.
9-70-0-0
PNC is no longer
heavily loaded.
Load applied to PNC has been
reduced to an acceptable level,
after it was previously heavily
loaded.
None.