To begin configuring one of these modules, right-click on the module in the Navigator and select
Change Submodule List from the menu.
The Change Submodule List
On the Change Submodule List, select the type of inputs or outputs that will be wired to the module,
and drag the selection to the content field in the left pane. For example:
As the description field indicates, the +10 VDC analog inputs in the example above do not require
the installation of jumpers on the module. The other choices for this module would require jumpers,
as listed in the reference table on the next page. It is important to be sure that the jumper
installation matches the
module’s configuration. If the channel is changed in the future, the module’s
configuration should be changed to match by following the steps above.
Configuring the Module Parameters
After choosing the submodule parameters of the module as described above, a subslot appears in
the Navigator, and the module’s configuration mismatch is cleared:
Double-click the subslot (not the module slot) in the Navigator to configure the module parameters.
The rest of the configuration for these modules is the same as the configuration of other VersaMax
modules. For a list of VersaMax Analog module subslot configuration choices and jumper settings,
refer to “Configuring Analog Modules that Have Jumpers” in the
VersaMax PROFINET Scanner
Manual,
GFK-2721.