Part II – Replacing the CPU
53
12
•
The option string will be written to the CPUs, after which they will automatically reboot. After
the reboot is complete, the dialog box for
Step 7
will display to update the settings to the
new unit. The option to skip the task is available if this has already been done.
Figure 12-14
Step 7 – Copy Setting dialog box
•
Finally, the dialog box for
Step 8
will display. Commissioning the new CPU will activate all of
the relaying and protection algorithms in the unit. Click the
Finish
button to complete the
process.
Figure 12-15
Step 8 – Set CPU Commission dialog box