Configuring the switchgear for remote communications
22
6
Step 8
: Install Remote HMIs.
See
Installing and configuring remote HMI software on page 25
.
Step 9
: Verify communication between Remote HMI and CPUs.
See Chapter 5.2. [dk: there is no section 5.2?]
6.1 Setting IP addresses for remote communication
6.1.1 HMI IP address
To change the HMI IP address
1.
For the HMI touchscreen computer, login to the Operating System as Administrator. See
Administrator access to the operating system on page 61
for details.
2.
Open the
Control Panel
, and then open the
Network Connections
dialog box.
3.
Double-click the
Local Area Connection 1
.
4.
In the
TCP/IP Properties
tab, set the new Local HMI IP address. Set the subnet mask to a
value compatible with the segment on which it resides.
By default the subnet mask is set to 255.255.255.0. The default touchscreen HMI IP address is
192.168.1.1 as delivered. The default IP address for each additional touchscreen HMI is
incremented by 1 in the right-most address.
6.1.2 CPU IP address
To change the CPU IP addresses
1.
On the
Main Menu
, click
User Settings
.
2.
Click
HMI Preferences
.
3.
Click
Communication
.
4.
Select either
CPU A
or
CPU B
by clicking the appropriate button.
5.
Enter the new IP address. The IP address format is X.X.X.X where X is from 0 to 255.
Содержание Entellisys DEH-230
Страница 1: ...GE Entellisys Low Voltage Switchgear System Administrator Manual ...
Страница 4: ......
Страница 8: ...System administrator roles and responsibilities 8 1 ...
Страница 10: ...Pre programming settings prior to switchgear arrival 10 2 2 ...
Страница 12: ...Commissioning the switchgear 12 3 ...
Страница 20: ...Time synchronization 20 5 ...
Страница 28: ...Installing and configuring remote HMI software 28 7 ...
Страница 32: ...Settings files and offline system configuration 32 8 Figure 8 3 Settings file compare screen ...
Страница 40: ...System archives 40 10 ...
Страница 44: ...Feature options 44 11 ...
Страница 54: ...Preparing and configuring a replacement CPU 54 12 ...
Страница 60: ...Other maintenance functions 60 13 ...
Страница 62: ......