Passwords
18
4
Figure 4-6
Breaker Control screen
•
The CPU reserves a communication port for the HMI with the Local HMI flag set. The CPUs
can support up to 8 simultaneous communication ports for Modbus clients. Once the limit is
exceeded, clients will be blocked until a port is free. The Local HMI flag has special ports
reserved for its use to prevent other clients from locking it out.
NOTE:
All In-Gear and Near-Gear Touchscreen HMIs should have the “Local HMI” set.
To set an HMI as a local HMI
1.
On the
Main Menu
, click the
Maintenance
button. The button will only be displayed if access
is allowed with the current login permissions.
2.
Click the
Modbus Security
tab.
3.
Select the
Local HMI
check box as shown in Figure 4-5.
4.
Click the
OK
button to save changes (or click
Cancel
to cancel changes).