Part II – Replacing the CPU
51
12
•
Apply power to the new CPU and allow 2 minutes for the device to self-initialize prior to
performing
Step 4
. If the new CPU is known to already have an IP address as specified in the
Step 4
dialog box, select the
Skip This Task
check box prior to clicking
Next
. Otherwise, leave
the check box cleared and just click
Next
.
Figure 12-10
Step 4 – Set Original IP dialog box
•
A confirmation dialog box will display asking for confirmation that the old CPU has been
replaced and the new CPU is installed and has been powered on for at least 2 minutes.
Figure 12-11
Entellisys LVS HMI dialog box