Programming Site Data
1-23
April 2008
Setting up RTD Inputs
Option cards with RTD inputs have a temperature range of –100 ° to
350 °C. Complete the following steps to set up the two RTD inputs of
an option card installed in Slot x:
1.
Use the [
←]
and [
→]
and the
[F1]-[F4]
keys to select the desired
slot number.
2.
Press
[F1]
to set up RTD input A or
[F2]
to set up RTD input B.
Note:
The setup of RTD input A is used as an example. Identical
procedures would be used to set up RTD input B.
3.
Enter a label of up to eight characters and press
[ENT]
.
4.
At the Input Measurement prompt, press
[F1] = OFF
to disable RTD
input A and return to the previous prompt, or press
[F2] = TEMP
to
enable RTD input A.
5.
Enter the
Zero Value
for the low end of the chosen input range and
press
[ENT]
.
6.
Enter the
Full Scale Value
for the high end of the chosen input
range and press
[ENT]
.
7.
Press
[F1]
-
[F2]
to set up another input or press
[EXIT]
to select
another slot for set up.
For instructions on setting up additional inputs and/or outputs
proceed to the appropriate section. Otherwise, press
[EXIT]
to return to
the main
I/O
menu prompt.
Entering the Zero Cutoff
Near zero flow, the Model GC868’s readings may fluctuate due to
small offsets caused by thermal drift or similar factors. To force a
zero reading when there is minimal flow, enter a zero cutoff value as
described below:
1.
At the main I/O menu prompt, press
[F3] = ZERO.
2.
Enter the desired
Zero Cutoff
value and press the
[ENT]
key. A
value of 0.1 ft/s (0.03 m/s) is recommended, but values from 0–1
ft/s (0–0.3 m/s) are acceptable. The menu returns to the main I/O
prompt.
Содержание DigitalFlow GC868
Страница 8: ...Chapter 1 ...
Страница 61: ...Chapter 2 ...
Страница 78: ...Chapter 3 ...
Страница 91: ...Chapter 4 ...
Страница 105: ...Chapter 5 ...
Страница 106: ...Clearing Data Introduction 5 1 Reset Totals 5 2 Deleting Site Files 5 3 Deleting Log Files 5 4 ...
Страница 111: ...Chapter 6 ...
Страница 123: ...Appendix A ...
Страница 132: ...Appendix B ...
Страница 133: ...Data Records Option Cards Installed B 1 Initial Setup Data B 2 ...
Страница 136: ...Appendix C ...
Страница 156: ...Appendix D ...