March 2008
1-52
Programming Site Data
Setting Up the Analog Inputs
Complete the following steps to set up the two 4-20 mA analog inputs
of an option card installed in
Slot x
:
Note:
For information on programming cards with RTD inputs, see
the next page.
1.
Press
[F1]
to set up input A or
[F2]
to set up input B.
Note:
The set up of input A is used as an example in this manual.
Identical procedures would be used to set up input B.
2.
Enter a
Label
of up to eight characters for input A and press
[ENT]
.
3.
Press
[F1]=OFF
to disable input A and return to the previous
prompt, or press
[F2]=TEMP or [F3]=SPEC
to designate the
Input
Measurement
as a temperature or special input, respectively.
•
If you select
TEMP
, skip to step 6 below.
•
If you select
OTHER, complete the following steps.
4.
Enter an
Input Name
and press
[ENT]
.
5.
Enter a
Unit
of measurement for input A and press
[ENT]
.
6.
Enter a value for the
Base
(low end) of the chosen input range and
press
[ENT]
.
7.
Enter a value for the
Full Scale
(high) end of the chosen input
range and press
[ENT]
.
8.
Press
[F1]
-
[F2]
to set up another input or press
[EXIT]
to select
another slot for setup.
For instructions on setting up additional inputs and/or outputs
proceed to the appropriate section. Otherwise, press
[EXIT]
twice to
return to the
Global Program
prompt.
Содержание DigitalFlow DF868
Страница 7: ...Chapter 1 ...
Страница 75: ...Chapter 2 ...
Страница 91: ...Chapter 3 ...
Страница 105: ...Chapter 4 ...
Страница 116: ...Chapter 5 ...
Страница 117: ...Clearing Data Introduction 5 1 Clearing Totalized Data 5 2 Deleting Site Files 5 2 Deleting Log Files 5 3 ...
Страница 121: ...Chapter 6 ...
Страница 132: ...Appendix A ...
Страница 142: ...Appendix B ...
Страница 143: ...Data Records Option Cards Installed B 1 Initial Setup Data B 2 ...
Страница 149: ...Appendix C ...
Страница 169: ...Appendix D ...