March 2008
1-56
Programming Site Data
MODBUS Register Map
When equipped with the optional MODBUS output card, the DF868
flow transmitter can send flow data and diagnostic information to a
flow computer (or SCADA) serially, using a Gould-type RTU
protocol. In this case, only the MODBUS function command, 3 (read
multiple registers), 6 (write multiple registers) is valid. The format for
the data exchange is as follows:
•
The
send
command (initiated by the host flow computer or
controller) comes in the form:
[time delimiter]<Addr><3><First Register MSB>
<First Register LSB><Register Count MSB>
<Register Count LSB><CRC Low><CRC High>[time delimiter]
•
The response (initiated by the host flow computer or controller)
comes in the form:
[time delimiter]<Addr><3><Byte count><Data.........>
<CRC Low><CRC High>[time delimiter]
The format for the returned data types is as follows:
•
Integer (16 bit Integer) <MSB><LSB>
1 Register - 16 bit integer
•
Integer (32 bit IntegerI) <MSB><LSB><LSB><LSB>
2 Register - 32 bit integer
•
Floating Point (FP) <EXP><MAN><MAN><MAN>
2 Registers - 32 bit IEEE floating point number
To request specific parameters from the DF868 via the MODBUS, the
control system must access the appropriate register number, as shown
in Table 1-26 on the next page. Only registers 1-108 are available
with the DF868 for MODBUS communications. Registers 508-512
are used by the DF868 to store the MODBUS parameters.
Note:
If you request Ch2 or AVE data from a 1-Channel meter, the
values will all be zero.
Содержание DigitalFlow DF868
Страница 7: ...Chapter 1 ...
Страница 75: ...Chapter 2 ...
Страница 91: ...Chapter 3 ...
Страница 105: ...Chapter 4 ...
Страница 116: ...Chapter 5 ...
Страница 117: ...Clearing Data Introduction 5 1 Clearing Totalized Data 5 2 Deleting Site Files 5 2 Deleting Log Files 5 3 ...
Страница 121: ...Chapter 6 ...
Страница 132: ...Appendix A ...
Страница 142: ...Appendix B ...
Страница 143: ...Data Records Option Cards Installed B 1 Initial Setup Data B 2 ...
Страница 149: ...Appendix C ...
Страница 169: ...Appendix D ...