4. APPLICATION
GEK-98514B
BUS1000 Busbar Protection
4-1
4.
4.
4.
4.
APPLICATION
APPLICATION
APPLICATION
APPLICATION
The BUS1000 system has been designed for bus protection in high voltage substations from 30 KV to 500
KV. Its main characteristics are:
•
Short operation time
, especially where fault levels are high, in order to minimise damage to the
switchgear and assist system stability. The BUS1000 is characterised by a high speed selective
detection and clearing of any fault produced in the protected area.
•
Careful design to operate on internal faults
. Busbar faults are rear, only by regular comprehensive
routine testing of the BUS1000 can the desired reliability be achieved.
•
Remain stable during all external faults
. Since many more faults occur externally to busbars than
internally, busbar protection is called upon to stabilise many more times than to operate. The protection
stability (correct operation with severe external faults that result in a saturation of one of the line current
transformers), is assured by selecting the adequate restraint percentage, depending only on the total
resistance of the saturated circuit seen from the relay.
•
Discriminate correctly
, that is decide on which section of the busbars the fault has occurred, and then
trip rapidly only those circuit breakers connected to that section.
•
Immune from misoperation
.
•
The protection does not require the use of dedicated current transformers
, neither need the latter
be of the same relation and characteristics for all the positions associated with the protected bus. Special
intermediate current transformers with the appropriate characteristics and relation are provided as part of
the protection system. This BUS1000 feature makes its application possible in existing facilities.
•
The BUS1000 system is provided for its application in double bar arrangements with air switches per
each position, with latching relays. These relays type HLB connects the secondary currents of the
auxiliary CT's (1 Amp. rated current) to the input of its corresponding differential unit (the same bar to
which the position is connected.
Содержание BUS1000
Страница 6: ......
Страница 8: ......
Страница 27: ...5 HARDWARE DESCRIPTION GEK 98514B BUS1000 Busbar Protection 5 3 Figure 7 1 BBD RACK Figure 7 2 BTR RACK ...
Страница 28: ...5 HARDWARE DESCRIPTION 5 4 BUS1000 Busbar Protection GEK 98514B Figure 7 4 BAR RACK Figure 7 5 BFR RACK ...
Страница 34: ...5 HARDWARE DESCRIPTION 5 10 BUS1000 Busbar Protection GEK 98514B ...
Страница 36: ...6 RECEIVING HANDLING AND STORAGE 6 2 BUS1000 Busbar Protection GEK 98514B ...
Страница 54: ...8 FINAL INSTALLATION AND COMMISSIONING 8 4 BUS1000 Busbar Protection GEK 98514B ...
Страница 56: ...9 TESTS AND PERIODICAL MAINTENANCE 9 2 BUS1000 Busbar Protection GEK 98514B ...
Страница 57: ...10 FIGURES GEK 98514B BUS1000 Busbar Protection 10 1 10 10 10 10 FIGURES FIGURES FIGURES FIGURES ...
Страница 66: ...10 FIGURES 10 10 BUS1000 Busbar Protection GEK 98514B ...
Страница 70: ...11 DIMENSIONS 11 4 BUS1000 Busbar Protection GEK 98514B FIGURE 19 POWER SUPPLY OR THYRITE BOXES 226B2211F18 ...
Страница 71: ...11 DIMENSIONS GEK 98514B BUS1000 Busbar Protection 11 5 FIGURE 20 BREAKER BLOCK DIAGRAM 226B2211F23 ÿ ÿ ÿ ÿ ÿ ...
Страница 74: ...11 DIMENSIONS 11 8 BUS1000 Busbar Protection GEK 98514B FIGURE 23 CABINET 226B2211F21 ...
Страница 104: ...13 SCHEMATICS DOUBLE BUSBAR 13 16 BUS1000 Busbar Protection GEK 98514B ...
Страница 107: ...13 SCHEMATICS DOUBLE BUSBAR GEK 98514B BUS1000 Busbar Protection 13 19 16 TEST UNIT ZONES A B 226B6429F16 ...
Страница 121: ...13 SCHEMATICS DOUBLE BUSBAR GEK 98514B BUS1000 Busbar Protection 13 33 31 POWER SUPPLY AUXILIARY CIRCUITS 226B6429F31 ...
Страница 123: ...13 SCHEMATICS DOUBLE BUSBAR GEK 98514B BUS1000 Busbar Protection 13 35 43 SIGNALLING CONTACT OUTPUTS 226B6429F43 ...
Страница 124: ...13 SCHEMATICS DOUBLE BUSBAR 13 36 BUS1000 Busbar Protection GEK 98514B CABINETS INTERCONNECTIONS 226B6429F44 ...